Issue Date: 1/17/02
NRC Inspection Manual IIPB
| PROGRAM APPLICABILITY: | 2515 |
| CORNERSTONE: | ALL |
| INSPECTION BASIS: | The NRC's revised inspection program includes three parts: baseline inspections; generic
safety issues and special inspections; and supplemental inspections performed as a result of
risk significant performance issues. The inspection program is designed to apply NRC
inspection assets in an increasing manner when risk significant performance issues are
identified, either by inspection findings evaluated using the significance determination
process (SDP) or when performance indicator thresholds are exceeded. Accordingly,
following the identification of an inspection finding categorized as risk significant (i.e.,
white, yellow, or red) via the SDP, or when a performance indicator exceeds the "licensee
response band" threshold, the NRC regional office will perform supplemental
inspection(s). The scope and breadth of these inspections will be based upon the guidance
provided in the NRC's assessment "Action Matrix" and the Supplemental Inspection Table
(included in 2515 Appendix B). The supplemental inspection program is designed to
support the NRC's goals of maintaining safety, enhancing public confidence, improving
the effectiveness and efficiency of the regulatory process, and reducing unnecessary
regulatory burden.
This procedure provides the supplemental response for one or two White inputs in a strategic performance area. The guidance provided in this procedure was developed with consideration of the following boundary conditions: supplemental inspection will not be done for single or multiple green issues; |
|
| 01.01 | To provide assurance that the root causes and contributing causes of risk significant performance issues are understood. |
| 01.02 | To provide assurance that the extent of condition of risk significant performance issues is identified. |
| 01.03 | To provide assurance that licensee corrective actions to risk significant performance issues are sufficient to address the root causes and contributing causes, and to prevent recurrence. |
In order to provide for adequate protection of public health and safety, once a risk significant performance issue is identified, the NRC needs to ensure that licensees take actions to identify the causes of the performance issue and preclude repetition. The most effective and efficient way for the NRC to accomplish this objective is allow the licensee the opportunity to perform their own evaluation of the performance issue, and then perform a review of the licensee's evaluation. The following inspection requirements represent a comprehensive set of attributes related to problem identification, root cause analysis, and establishment of corrective actions.
In order to ensure that the causes of the performance issue are identified and that effective corrective actions are taken to prevent recurrence, it is expected that the licensee's evaluation will generally need to address each of the inspection requirements; however, the depth of the licensee's analysis may vary depending on the significance and complexity of the issue(s). In some cases, the answers to specific inspection requirements will be self-evident with little additional review or analysis required.
In completing this inspection procedure, it is not intended that NRC inspectors perform an independent evaluation of the performance issue, nor is the intent to merely verify that an evaluation has been performed without assessing its adequacy. Rather, inspectors should sufficiently challenge aspects of the licensee's evaluation, as necessary to ensure that the cause(s) of the performance issues have been identified and that appropriate corrective actions have been taken to prevent recurrence. Inspectors may utilize information previously obtained as part of the baseline inspection program to fulfill the inspection requirements; however, the inspection report associated with this inspection should contain the NRC's assessment of the licensee's evaluation for each inspection requirement. The results of this inspection should be documented in accordance with the specific guidance contained in IMC 0612 (formerly 0610*) for documenting supplemental inspections.
Significant weaknesses in the licensee's actions to address the performance issue may be subject to additional agency actions, including additional enforcement actions or an expansion of this procedure as necessary to independently acquire the information necessary to satisfy the inspection requirements. In general, licensees should be given an opportunity to correct any identified deficiencies prior to re-inspection. Also, for inspection findings, the original performance issue will remain open and will not be removed from the action matrix until the weaknesses are addressed and corrected. For significant weaknesses in the licensee's actions to address a performance issue that is associated with a performance indicator, a parallel inspection finding will be opened and given the same color as the PI; however, the finding will not be double counted in the action matrix. Also, for those performance indicators that include fault exposure hours, the provision contained in NEI 99-02 to remove the fault exposure hours after four quarters requires successful closure of any open items identified during this inspection. Programmatic weaknesses associated with the licensee's evaluation of the performance issue will also be documented in the inspection report and additional focus will be given to those areas during the next annual problem identification and resolution baseline inspection.
Should new or additional examples of performance issues (non-programmatic) be identified by this inspection or by the licensee during their evaluation, the new issues will be categorized using the SDP and the corresponding supplemental inspection procedure will be performed. Supplemental inspections will also be performed if additional examples of performance issues are reported via performance indicators (PIs) that result in crossing a new PI threshold. Additional supplemental inspections will generally not be performed if the new or additional examples of performance issues reported via PIs do not result in crossing a new PI threshold.
The following inspection requirements are generally applicable for both single inspection findings and for performance issues reported by PIs that might represent more than one independent event (e.g. four scrams). In the case where the white performance issue is due to multiple events or occurrences, it is expected that the licensee's evaluation would address each of the events or occurrences. This could be accomplished either by doing independent evaluations for each occurrence or by doing one collective evaluation.
| 02.01 | Problem Identification |
| a. Determine that the evaluation identifies who (i.e. licensee, self revealing, or NRC), and under what conditions the issue was identified. | |
| b. Determine that the evaluation documents how long the issue existed, and prior opportunities for identification. | |
| c. Determine that the evaluation documents the plant specific risk consequences (as applicable) and compliance concerns associated with the issue. | |
| 02.02 | Root Cause and Extent of Condition Evaluation |
| a. Determine that the problem was evaluated using a systematic method(s) to identify root cause(s) and contributing cause(s). | |
| b. Determine that the root cause evaluation was conducted to a level of detail commensurate with the significance of the problem. | |
| c. Determine that the root cause evaluation included a consideration of prior occurrences of the problem and knowledge of prior operating experience. | |
| d. Determine that the root cause evaluation included consideration of potential common cause(s) and extent of condition of the problem. | |
| 02.03 | Corrective Actions |
| a. Determine that appropriate corrective action(s) are specified for each root/contributing cause or that there is an evaluation that no actions are necessary. | |
| b. Determine that the corrective actions have been prioritized with consideration of the risk significance and regulatory compliance. | |
| c. Determine that a schedule has been established for implementing and completing the corrective actions. | |
| d. Determine that quantitative or qualitative measures of success have been developed for determining the effectiveness of the corrective actions to prevent recurrence. |
General Guidance
This inspection procedure is designed to be used to assess the adequacy of the licensee's evaluation of White issues. As such, a reasonable time (generally within 30-60 days) should be allowed for the licensee to complete their evaluation; however, all corrective actions may not be fully completed upon commencement of this procedure. Implementation of these corrective actions may be verified during subsequent baseline inspections such as the annual problem identification and resolution.
The following sections of the procedure are provided as guidance to help the inspector fulfill the specific inspection requirements contained in section 02 above. It is not intended that the inspector verify that the licensee's evaluation of the White issue contains every attribute contained in the inspection guidance section. The intent is that the inspector use the guidance sections of the procedure to look for weaknesses in the licensee's evaluation that might indicate an issue associated with one of the inspection requirements.
Definitions
Root Cause(s) are defined as the basic reason(s) (i.e., hardware, process, human performance), for a problem, which if corrected, will prevent recurrence of that problem.
Contributing Cause(s) are defined as causes that by themselves would not create the problem, but are important enough to be recognized as needing corrective action. Contributing causes are sometimes referred to as causal factors. Causal factors are those actions, conditions, or events which directly or indirectly influence the outcome of a situation or problem.
Repeat occurrences are defined as two or more independent conditions which are the result of the same basic causes.
Common Cause is defined as multiple failures (i.e., two or more) of plant equipment or processes attributable to a shared cause.
Extent of Condition is defined as the extent to which the root causes of an identified problem have impacted other plant processes, equipment, or human performance.
Consequences are defined as the actual or potential outcome of an identified problem or condition.
Specific Guidance
| 03.01 | Problem Identification | |
| a. The evaluation should state how and by whom the issue was identified. When appropriate, failure of the licensee to identify the problem at a precursor level should be evaluated. Specifically, the failure of the licensee to identify a problem at an early stage may be indicative of a more substantial problem. Examples would include a failure of the licensee's staff to enter a recognized non-compliance into the corrective action program, or raise safety concerns to management, or the failure to complete corrective actions for a previous problem resulting in further degradation. If the NRC identified the White issue, the evaluation should address why licensee processes such as peer review, supervisory oversight, inspection, testing, self assessments, or quality activities did not identify the problem. | ||
| b. The evaluation should state when the problem was identified, how long the condition(s) existed, and whether there were prior opportunities for correction. For example, if a maintenance activity resulted in an inoperable system that was not detected by post-maintenance testing or by quality assurance oversight, the reasons that the testing and quality oversight did not detect the error should be included in the problem identification statement and addressed in the root cause evaluation. | ||
| c. The evaluation should address the plant specific risk consequences of the issue. A plant specific assessment may better characterize the risk associated with the White issue due to the generic nature of the performance indicators. For conditions that are not easily assessed quantitatively, such as the unavailable of security equipment, a qualitative assessment should be completed. The evaluation should also include an assessment of compliance. As applicable, some events may be more appropriately assessed as hazards to plant personnel or the environment. The inspector's review of the risk assessment should be coordinated with the Senior Reactor Analyst. | ||
| 03.02 | Root Cause and Extent of Condition Evaluation | |
| a. The licensee's evaluation should generally make use of a systematic method(s) to identify root cause(s) and contributing cause(s). The root cause evaluation methods that are commonly used in nuclear facilities are: | ||
| ||
| The licensee may use other methods to conduct the root cause evaluations.
A systematic evaluation of a problem using one of the above methods should normally include: | ||
|
||
-hardware issues could include design, materials, systems aging, and environmental conditions; -process issues could include procedures, work practices, operational policies, supervision and oversight, preventive and corrective maintenance programs, and quality control methods; and -human performance issues could include training, communications, human system interface, and fitness for duty. |
||
| b. The root cause evaluation should be conducted to an adequate level of detail, considering the significance of the problem. | ||
|
||
| The depth of a root cause evaluation is normally achieved by repeatedly asking the question "Why?" about the
occurrences and circumstances that caused or contributed to the problem. Once the analysis has developed all of the
causes for the problem (i.e., root, contributory, programmatic), the evaluation should also look for any relationships
among the different causes.
The depth of the root cause evaluation may be assessed by: | ||
| ||
c. The root cause evaluation should include a proper consideration of repeat occurrences of the same or similar problems at the facility and knowledge of prior operating experience. This review is necessary to help in developing the specific root and contributing causes and also to provide indication as to whether the White issue is due to a more fundamental concern involving weaknesses in the licensee's corrective action program.
The evaluation should:
d. The root cause evaluation should include a proper consideration of the extent of condition of the problem including whether other systems, equipment, programs or conditions could be effected. The evaluation should:
| 03.03 | Corrective Actions |
| The proposed corrective actions to the root and contributing causes should: | |
| a. Address each of the root and contributing causes to the White
issue and the extent of condition of the issue. The corrective
actions should be clearly defined. Examples of corrective
actions may include, but are not limited to, modifications,
inspections, testing, process or procedure changes, and training.
The proposed corrective actions should not create new or different problems as a result of the corrective action. If the licensee determines that no corrective actions are necessary, the basis for this decision should be documented in the evaluation. | |
| b. Include consideration of the results of the licensee's risk
assessment of the issue in prioritizing the type of corrective
action chosen. Attention should be given to solutions that
involve only changing procedures or providing training as they
are sometimes over-utilized. In such cases, consideration should
be given to more comprehensive corrective actions such as
design modifications. The corrective action plan should also
include a review of the regulations to ensure that if compliance
issues exist, the plan achieves compliance.
Also, the licensee should ensure that: | |
| c. The corrective actions are assigned to individuals or organizations that are appropriate to ensure that the actions are taken in a timely manner. Also, the licensee should ensure that there is a formal tracking mechanism established for each of the specific corrective actions. | |
| d. A method exists to validate the effectiveness of the overall corrective action plan. Specifically, a method should be established to measure, either quantitatively or qualitatively, the effectiveness of the corrective actions. Effective methods would include, but are not limited to, assessments, audits, inspections, tests, and trending of plant data, or follow-up discussions with plant staff. |
It is estimated that this procedure will take between 16 and 40 man-hours to complete for each White issue. The inspector or inspectors assigned should be familiar with the discipline associated with the subject of the licensee's evaluation. For planning purposes, a resource estimate near the lower end of the scale should be used for licensees with corrective actions programs that have been determined to be thorough during the annual inspection for the identification and resolution of problems. For licensees with corrective action programs that have been previously determined to be ineffective, a resource estimate near the higher end of the scale should be used.
END