Skip to main content

Alert

The NRC is shutdown due to the lapse in appropriations. Exempted activities to maintain critical health and safety activities and progress on critical activities, including activities outlined in Executive Order 14300, as described in the OMB Approved NRC Lapse Plan will continue.

Bulletin 86-01: Minimum Flow Logic Problems That Could Disable RHR Pumps

                                                       SSINS No.: 6820
                                                       OMB No.: 3150-0012
                                                       IEB 86-01

                                UNITED STATES
                        NUCLEAR REGULATORY COMMISSION
                    OFFICE OF INSPECTION AND ENFORCEMENT
                            WASHINGTON, DC  20555

                                May 23, 1986

IE COMPLIANCE BULLETIN NO. 86-01:  MINIMUM FLOW LOGIC PROBLEMS THAT COULD 
                                   DISABLE RHR PUMPS 

Addressees: 

All GE boiling water reactor (BWR) facilities holding an operating license 
(OL) or a construction permit (CP). 

Purpose: 

The purposes of this bulletin are: (1) to inform BWR licensees and 
applicants of a recently identified problem with the minimum flow logic for 
which a single failure could disable all RHR pumps, (2) to request that 
licensees affected by the problem immediately provide appropriate 
instructions and training to plant operators on how to recognize the problem 
if it occurs and take appropriate mitigating actions, (3) to request that 
licensees notify the NRC of the existence of the problem at their facility 
within 7 days of receipt of this bulletin, and (4) to request that licensees 
inform the NRC of measures taken to correct design or installation problems 
that are identified as a result of this bulletin. 

Description of Circumstances: 

During a recent review of IE Information Notice 85-94, "Potential For Loss 
Of Minimum Flow Paths Leading To ECCS Pump Damage During A LOCA," the 
Pilgrim Nuclear Power Plant discovered that a single failure under certain 
accident sequences could result in all RHR minimum flow bypass valves being 
signaled to close while all other pump discharge valves are also closed. 
This condition could result in no flow through the RHR pumps and could lead 
to the pumps running dead headed with potential for pump damage in a few 
minutes. If this single failure occurred in conjunction with an automatic 
start of the RHR system, RHR pump damage may occur if unrecognized by the 
operator. This event could disable RHR functions including Low Pressure 
Coolant Injection (LPCI), head spray, drywell spray, shutdown cooling, torus 
spray and suppression pool cooling. As a result of the loss of suppression 
pool cooling over a long period of time, core spray pumps could ultimately 
lose net positive suction head and also be unavailable. 

The NRC staff has judged that the overall probability of a serious core 
damage accident due to this problem is low. Nevertheless, such a single 
failure vulnerability is not in compliance with the regulatory requirement 
for independence in emergency core cooling systems and could compromise 
several important systems. 


8605230308 
.

                                                            IEB 86-O1
                                                            May 23, 1986
                                                            Page 2 of 3

GE's initial review identified the following plants with some potential for 
having the single failure problem: Pilgrim; Browns Ferry 1, 2 and 3; Peach 
Bottom 2 and 3; Duane Arnold; Millstone 1; Monticello; Quad Cities 1 and 2; 
Dresden 2 and 3; Cooper; and Fermi 2. The staff understands that GE has 
notified these potentially affected facilities and informal communications 
from GE indicate that the list was narrowed to Pilgrim, Quad Cities and 
possibly Dresden during preparation of the bulletin. The above listed plants
are being provided the bulletin by telecopy. Since there is not complete 
certainty that other BWR's do not have the problem, they are also addressed 
by this bulletin. Their copies are being sent by mail. 

At Pilgrim, to prevent the pump from running dead headed, each pair of RHR 
pumps is provided with a minimum flow bypass capability. The minimum flow 
bypass consists of an orificed flow bypass which allows a flow of 
approximately 10 percent of rated flow. The minimum flow bypass lines for 
each pair of RHR pumps are connected to a single line and controlled by a 
single minimum flow bypass valve. The minimum flow bypass valve is normally 
open. The valve will close upon sensing flow in either of the RHR loops. 

The current logic configuration for Pilgrim minimum flow bypass valves is 
that a high flow signal from either the A or B RHR loops will close both A 
and B bypass valves. Thus, a postulated single failure of a flow sensing 
instrument may result in all RHR pumps running without bypass flow. If this 
failure occurs during an event with a high drywell signal or low water level
signal, such as during small or intermediate size loss of cooling accidents 
(LOCA) or spurious actuation, the RHR pumps may start and run dead headed. 

One of the potential fixes being proposed by GE is to remove the automatic 
closing signal from the RHR minimum flow bypass valves. This fix will result
in some of the LPCI flow being diverted through the minimum flow line. For 
other RHR modes of operation, the values may be manually closed. 

Although safety analyses may justify this interim fix, there are a number of
problems that need to be considered. For example, on many plants the minimum
flow bypass valves must be closed during shutdown cooling in order to 
prevent draining the reactor vessel inventory to the torus. The minimum flow 
bypass valves are considered containment isolation valves on some plants. 

                  REQUIRED ACTION FOR GE BWR FACILITIES 

1.   Promptly determine whether or not your facility has this single failure
     vulnerability. 

2.   If the problem exists, immediately instruct all operating shifts of the
     problem and measures to recognize and mitigate the problem. 

3.   Within 7 days of receipt of this bulletin, provide (a) a written report
     to the NRC which identifies whether or not this problem exists at your 
     facility, (b) if the problem exists, identify the short-term 
     modifications to plant operating procedures or hardware that have been 
     or are being implemented to assure safe plant operations. 

.

                                                            IEB 86-01
                                                            May 23, 1986
                                                            Page 3 of 3


4.   If the problem exists, provide a written report within 30 days of 
     receipt of this bulletin informing the NRC of the schedule for 
     long-term resolution of problems that are identified as a result of 
     this bulletin. 

Should a licensee determine that any action requested by this bulletin 
jeopardizes overall plant safety, the NRC should be notified of that fact 
and provided with appropriate justification for not implementing the 
requested action. Such notification shall be made within 7 days of receipt 
of this bulletin. 

The written reports shall be submitted to the appropriate Regional 
Administrator under oath or affirmation under provisions of Section 182a, 
Atomic Energy Act of 1954, as amended. Also, the original copy of the cover 
letters and a copy of the reports shall be transmitted to the U.S. Nuclear 
Regulatory Commission, Document Control Desk, Washington, D.C. 20555 for 
reproduction and distribution. 

This request for information was approved by the Office of Management and 
Budget under a blanket clearance number 3150-0011. Comments on burden and 
duplication may be directed to the Office of Management and Budget, Reports 
Management, Room 3208, New Executive Office Building, Washington, D. C. 
20503. 

If you have questions regarding this matter, please contact the Regional 
Administrator of the appropriate NRC Regional Office or one of the technical
contacts listed below. 




                              James M. Taylor, Director
                              Office of Inspection and Enforcement

Technical Contacts:      Eric Weiss, IE 
                         (301) 492-9005 

                         M. Wayne Hodges, NRR 
                         (301) 492-7483 

Attachment:    List of Recently Issued IE Bulletins  
 

Page Last Reviewed/Updated Tuesday, March 09, 2021

Page Last Reviewed/Updated Tuesday, March 09, 2021