LICENSEE: SOUTH CAROLINA ELECTRIC & GAS CO. SITE: SUMMER 1 EN NUMBER:30811 DOCKET: 05000395 EVENT DATE: 07-30-96 RX TYPE: PWR EVENT TIME: 00:00 VENDORS: W-3-LP NOTIFY DATE: 07-31-96 EMERGENCY CLASS: N/A REGION: 2 STATE: SC TIME: 15:51 OPS OFFICER: RUDY KARSCH 10 CFR SECTION: CDEG 21.21(c)(3)(i) DEFECTS/NONCOMPLIANCE UNIT SCRAM RX INIT INITIAL MODE CURR CURRENT MODE CODE CRIT PWR PWR 1 N Y 75 POWER OPERATION 75 POWER OPERATION THREE BARTON MODEL-763 PRESSURE TRANSDUCERS TAKEN FROM STOCK HAD BROKEN STRAIN GAGE LEADS. THE LEAD FROM THE STRAIN GAGE WAS BROKEN LOOSE AT THE TERMINAL PIN. ITT BARTON HAS NOT ESTABLISHED A ROOT CAUSE FOR WHAT APPEARS TO BE A REPETITIVE FAILURE. THE LICENSEE INFORMED THE NRC RESIDENT INSPECTOR.