Event Notification Report for April 22, 2024
U.S. Nuclear Regulatory Commission
Operations Center
EVENT REPORTS FOR
04/21/2024 - 04/22/2024
Agreement State
Event Number: 57071
Rep Org: Alabama Radiation Control
Licensee: Alabama River Cellulose, LLC
Region: 1
City: Perdue Hill State: AL
County:
License #: Alabama RML 634
Agreement: Y
Docket:
NRC Notified By: Cason Coan
HQ OPS Officer: Sam Colvard
Licensee: Alabama River Cellulose, LLC
Region: 1
City: Perdue Hill State: AL
County:
License #: Alabama RML 634
Agreement: Y
Docket:
NRC Notified By: Cason Coan
HQ OPS Officer: Sam Colvard
Notification Date: 04/12/2024
Notification Time: 12:05 [ET]
Event Date: 04/11/2024
Event Time: 15:00 [CDT]
Last Update Date: 04/12/2024
Notification Time: 12:05 [ET]
Event Date: 04/11/2024
Event Time: 15:00 [CDT]
Last Update Date: 04/12/2024
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
10 CFR Section:
Agreement State
Person (Organization):
Defrancisco, Anne (R1DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
Defrancisco, Anne (R1DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
AGREEMENT STATE REPORT - STUCK OPEN SHUTTER
The following is a summary of information received from the Alabama Office of Radiation Control via email:
On April 11, 2024, at 1500 CST, a device (Ohmart/Vega, SH-F1, Model A-2102, Source SN 9254GK, 100 mCi Cs-137) was discovered to have a stuck open shutter during routine shutter checks. The device is in place and operational. The area around the vessel on which the device is mounted has been barricaded and marked for no entry. The licensee's plan is to replace the source holder with a new one. The licensee is getting a quote for replacement and installation with an estimated repair date of May 10, 2024.
The following is a summary of information received from the Alabama Office of Radiation Control via email:
On April 11, 2024, at 1500 CST, a device (Ohmart/Vega, SH-F1, Model A-2102, Source SN 9254GK, 100 mCi Cs-137) was discovered to have a stuck open shutter during routine shutter checks. The device is in place and operational. The area around the vessel on which the device is mounted has been barricaded and marked for no entry. The licensee's plan is to replace the source holder with a new one. The licensee is getting a quote for replacement and installation with an estimated repair date of May 10, 2024.
Agreement State
Event Number: 57073
Rep Org: SC Dept of Health & Env Control
Licensee: Medical University of South Carolina
Region: 1
City: Charleston State: SC
County:
License #: 081
Agreement: Y
Docket:
NRC Notified By: Korina Koci
HQ OPS Officer: Ernest West
Licensee: Medical University of South Carolina
Region: 1
City: Charleston State: SC
County:
License #: 081
Agreement: Y
Docket:
NRC Notified By: Korina Koci
HQ OPS Officer: Ernest West
Notification Date: 04/12/2024
Notification Time: 13:53 [ET]
Event Date: 04/12/2024
Event Time: 11:30 [EDT]
Last Update Date: 04/12/2024
Notification Time: 13:53 [ET]
Event Date: 04/12/2024
Event Time: 11:30 [EDT]
Last Update Date: 04/12/2024
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
10 CFR Section:
Agreement State
Person (Organization):
Defrancisco, Anne (R1DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
Defrancisco, Anne (R1DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
AGREEMENT STATE - MEDICAL UNDERDOSE
The following information was provided by the South Carolina Department of Health and Environmental Control (Department) via email:
"The South Carolina Department of Health and Environmental Control was notified via telephone at approximately 1301 [EDT] on 4/12/24, that a medical event had been discovered by the licensee on 4/12/24 at approximately 1130 [EDT]. The Medical University of South Carolina (MUSC) reports an underdose to a patient's liver during a Y-90 microsphere procedure by 78 percent of the prescribed 120 Gray (Gy) dose. The licensee estimates that the patient received 27 Gy, which is 22 percent of the intended 120 Gy dose. The licensee reports that the total dose or activity delivered differs from the prescribed dose or activity, as documented in the written directive, by 20 percent or more. The patient was notified of this medical event verbally.
"The licensee reports no immediate or ongoing concerns to public health and safety. Department inspectors will be dispatched to the facility to investigate this event. This event is still under investigation by the South Carolina Department of Health and Environmental Control."
A Medical Event may indicate potential problems in a medical facility's use of radioactive materials. It does not necessarily result in harm to the patient.
The following information was provided by the South Carolina Department of Health and Environmental Control (Department) via email:
"The South Carolina Department of Health and Environmental Control was notified via telephone at approximately 1301 [EDT] on 4/12/24, that a medical event had been discovered by the licensee on 4/12/24 at approximately 1130 [EDT]. The Medical University of South Carolina (MUSC) reports an underdose to a patient's liver during a Y-90 microsphere procedure by 78 percent of the prescribed 120 Gray (Gy) dose. The licensee estimates that the patient received 27 Gy, which is 22 percent of the intended 120 Gy dose. The licensee reports that the total dose or activity delivered differs from the prescribed dose or activity, as documented in the written directive, by 20 percent or more. The patient was notified of this medical event verbally.
"The licensee reports no immediate or ongoing concerns to public health and safety. Department inspectors will be dispatched to the facility to investigate this event. This event is still under investigation by the South Carolina Department of Health and Environmental Control."
A Medical Event may indicate potential problems in a medical facility's use of radioactive materials. It does not necessarily result in harm to the patient.
Agreement State
Event Number: 57074
Rep Org: Colorado Dept of Health
Licensee: Brighton United Methodist Church
Region: 4
City: Brighton State: CO
County:
License #: GL002235
Agreement: Y
Docket:
NRC Notified By: Kathryn Kirk
HQ OPS Officer: Ernest West
Licensee: Brighton United Methodist Church
Region: 4
City: Brighton State: CO
County:
License #: GL002235
Agreement: Y
Docket:
NRC Notified By: Kathryn Kirk
HQ OPS Officer: Ernest West
Notification Date: 04/12/2024
Notification Time: 16:43 [ET]
Event Date: 04/12/2024
Event Time: 00:00 [MDT]
Last Update Date: 04/12/2024
Notification Time: 16:43 [ET]
Event Date: 04/12/2024
Event Time: 00:00 [MDT]
Last Update Date: 04/12/2024
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
10 CFR Section:
Agreement State
Person (Organization):
Azua, Ray (R4DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
ILTAB, (EMAIL) (EMAIL)
Azua, Ray (R4DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
ILTAB, (EMAIL) (EMAIL)
AGREEMENT STATE REPORT - LOST EXIT SIGNS
The following is a summary of information received from the Colorado Department of Public Health and Environment via email:
Two SRB Technologies exit signs, model number: BX10GY, containing 10 curies each, of tritium (20 curies total) were determined to be lost by the licensee.
Colorado event number CO240010
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
The following is a summary of information received from the Colorado Department of Public Health and Environment via email:
Two SRB Technologies exit signs, model number: BX10GY, containing 10 curies each, of tritium (20 curies total) were determined to be lost by the licensee.
Colorado event number CO240010
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
Agreement State
Event Number: 57076
Rep Org: Colorado Dept of Health
Licensee: Nondestructive & Visual Inspection
Region: 4
City: Northglenn State: CO
County:
License #: CO1241-01
Agreement: Y
Docket:
NRC Notified By: Carrie Romanchek
HQ OPS Officer: Sam Colvard
Licensee: Nondestructive & Visual Inspection
Region: 4
City: Northglenn State: CO
County:
License #: CO1241-01
Agreement: Y
Docket:
NRC Notified By: Carrie Romanchek
HQ OPS Officer: Sam Colvard
Notification Date: 04/15/2024
Notification Time: 12:28 [ET]
Event Date: 03/24/2024
Event Time: 00:00 [MDT]
Last Update Date: 04/15/2024
Notification Time: 12:28 [ET]
Event Date: 03/24/2024
Event Time: 00:00 [MDT]
Last Update Date: 04/15/2024
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
10 CFR Section:
Agreement State
Person (Organization):
Young, Cale (R4DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
Young, Cale (R4DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
AGREEMENT STATE REPORT - BROKEN LOCK ON RADIOGRAPHY CAMERA
The following information was received from the Colorado Department of Public Health and Environment via email:
"This letter is serving as notification of an equipment failure under [Colorado Regulation] Section 4.52.2.3 and 5.38.1.3. A QSA Global 880 Delta camera was received from Source Production and Equipment Company, Inc. (SPEC), after being resourced. During the check-in procedure and mechanism check, it was discovered that the lock that controls access to the pigtail attachment was broken in the locked position. The camera was tagged out until it could be sent to Industrial Nuclear Company (INC), for repairs on 04/04/2024. The lock was repaired at INC, and the camera was returned to the licensee on 04/10/2024 with no issues."
Colorado Event Report ID: CO240011
The following information was received from the Colorado Department of Public Health and Environment via email:
"This letter is serving as notification of an equipment failure under [Colorado Regulation] Section 4.52.2.3 and 5.38.1.3. A QSA Global 880 Delta camera was received from Source Production and Equipment Company, Inc. (SPEC), after being resourced. During the check-in procedure and mechanism check, it was discovered that the lock that controls access to the pigtail attachment was broken in the locked position. The camera was tagged out until it could be sent to Industrial Nuclear Company (INC), for repairs on 04/04/2024. The lock was repaired at INC, and the camera was returned to the licensee on 04/10/2024 with no issues."
Colorado Event Report ID: CO240011
Power Reactor
Event Number: 57083
Facility: LaSalle
Region: 3 State: IL
Unit: [1] [] []
RX Type: [1] GE-5,[2] GE-5
NRC Notified By: Kelsey Smith
HQ OPS Officer: Tenisha Meadows
Region: 3 State: IL
Unit: [1] [] []
RX Type: [1] GE-5,[2] GE-5
NRC Notified By: Kelsey Smith
HQ OPS Officer: Tenisha Meadows
Notification Date: 04/20/2024
Notification Time: 13:51 [ET]
Event Date: 04/20/2024
Event Time: 07:04 [CDT]
Last Update Date: 04/20/2024
Notification Time: 13:51 [ET]
Event Date: 04/20/2024
Event Time: 07:04 [CDT]
Last Update Date: 04/20/2024
Emergency Class: Non Emergency
10 CFR Section:
50.72(b)(3)(iv)(A) - Valid Specif Sys Actuation
10 CFR Section:
50.72(b)(3)(iv)(A) - Valid Specif Sys Actuation
Person (Organization):
Betancourt-Roldan, Diana (R3DO)
Betancourt-Roldan, Diana (R3DO)
Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
---|---|---|---|---|---|---|
1 | N | Y | 100 | Power Operation | 100 | Power Operation |
AUTOMATIC ACTUATION OF EMERGENCY DIESEL GENERATORS
The following information was provided by the licensee via phone and email:
"At 0704 CDT on 4/20/24 with Unit 1 in Mode 1 at 100 percent power, an actuation of the emergency AC power system, specifically the Division 1 and Division 3 emergency diesel generators (EDGs) occurred during an unexpected loss of the Unit 1 system auxiliary transformer (SAT). The cause of the emergency AC power system auto-start was an unexpected loss of the Unit 1 SAT during switchyard maintenance. Bus 141Y did not fast transfer as designed resulting in the actuation of the Division 1 EDG. Division 3 EDG actuation is expected for this condition. The Division 1 and Division 3 EDGs automatically started as designed when the emergency AC power system valid actuation signal was received.
"This event is being reported in accordance with 10 CFR 50.72(b)(3)(iv)(A) as an event that results in a valid actuation of the emergency AC power system.
"There was no impact on the health and safety of the public or plant personnel. The NRC Resident Inspector has been notified."
The following additional information was obtained from the licensee in accordance with Headquarters Operations Officers Report Guidance:
Division 1 and Division 3 EDGs will remain in operation and loaded until the Unit 1 SAT is restored. This event resulted in the plant entering an unplanned 72 hour limiting condition for operation (LCO) in accordance with technical specification 3.8.1. The licensee is investigating the cause of the unexpected loss of the Unit 1 SAT and the failure of the bus 141Y fast transfer.
The following information was provided by the licensee via phone and email:
"At 0704 CDT on 4/20/24 with Unit 1 in Mode 1 at 100 percent power, an actuation of the emergency AC power system, specifically the Division 1 and Division 3 emergency diesel generators (EDGs) occurred during an unexpected loss of the Unit 1 system auxiliary transformer (SAT). The cause of the emergency AC power system auto-start was an unexpected loss of the Unit 1 SAT during switchyard maintenance. Bus 141Y did not fast transfer as designed resulting in the actuation of the Division 1 EDG. Division 3 EDG actuation is expected for this condition. The Division 1 and Division 3 EDGs automatically started as designed when the emergency AC power system valid actuation signal was received.
"This event is being reported in accordance with 10 CFR 50.72(b)(3)(iv)(A) as an event that results in a valid actuation of the emergency AC power system.
"There was no impact on the health and safety of the public or plant personnel. The NRC Resident Inspector has been notified."
The following additional information was obtained from the licensee in accordance with Headquarters Operations Officers Report Guidance:
Division 1 and Division 3 EDGs will remain in operation and loaded until the Unit 1 SAT is restored. This event resulted in the plant entering an unplanned 72 hour limiting condition for operation (LCO) in accordance with technical specification 3.8.1. The licensee is investigating the cause of the unexpected loss of the Unit 1 SAT and the failure of the bus 141Y fast transfer.
Power Reactor
Event Number: 57046
Facility: Fermi
Region: 3 State: MI
Unit: [2] [] []
RX Type: [2] GE-4
NRC Notified By: Trevor Jarrait
HQ OPS Officer: Adam Koziol
Region: 3 State: MI
Unit: [2] [] []
RX Type: [2] GE-4
NRC Notified By: Trevor Jarrait
HQ OPS Officer: Adam Koziol
Notification Date: 03/23/2024
Notification Time: 03:47 [ET]
Event Date: 03/23/2024
Event Time: 00:04 [EDT]
Last Update Date: 04/22/2024
Notification Time: 03:47 [ET]
Event Date: 03/23/2024
Event Time: 00:04 [EDT]
Last Update Date: 04/22/2024
Emergency Class: Non Emergency
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS Actuation - Critical 50.72(b)(3)(iv)(A) - Valid Specif Sys Actuation 50.72(b)(3)(v)(D) - Accident Mitigation
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS Actuation - Critical 50.72(b)(3)(iv)(A) - Valid Specif Sys Actuation 50.72(b)(3)(v)(D) - Accident Mitigation
Person (Organization):
Hills, David (R3DO)
Hills, David (R3DO)
Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
---|---|---|---|---|---|---|
2 | A/R | Y | 23 | Power Operation | 0 | Hot Shutdown |
EN Revision Imported Date: 4/23/2024
EN Revision Text: AUTOMATIC REACTOR TRIP
The following information was provided by the licensee via email:
"At 0004 EDT on March 23, 2024, with the unit in Mode 1 at 23 percent power, the reactor automatically scrammed due to high reactor pressure vessel pressure when the turbine bypass valves unexpectedly closed while attempting to lower generator MW to 55 MWe to support shutdown for a refueling outage. The scram was not complex, with systems responding normally post-scram, with the exception of the pressure control system. The transient occurred while lowering on turbine speed/load demand which caused a rise in pressure and power until the reactor protection system setpoint for reactor pressure high was exceeded and resulted in an automatic reactor scram. The plant was preparing to shut down for a refueling outage when the trip occurred.
"Operations responded and stabilized the plant. Reactor water level is being maintained at normal level. Decay heat is being removed by the main steam system to the main condenser using manual operation of the turbine bypass valves. All control rods inserted into the core.
"Due to the reactor protection system actuation while critical, this event is being reported as a four-hour, non-emergency notification per 10 CPR 50.72(b)(2)(iv)(B). Additionally, received expected [primary containment] isolations for Level 3: Group 13 drywell sumps, Group 15 [traverse in-core probe] TlPs (which was already isolated) and Group 4 [residual heat removal - shutdown cooling] RHR-SDC (which was already isolated). The primary containment isolation event is being reported under 10 CFR 50.72(b)(3)(iv)(A). Also, due to the main turbine bypass valves unexpectedly closing, this is also being reported under 10 CFR 50.72(b)(3)(v)(D).
"There was no impact to the health and safety of the public or plant personnel. The NRC Resident Inspector has been notified."
* * * UPDATE ON 4/22/24 AT 1448 EDT FROM WHITNEY HEMINGWAY TO ADAM KOZIOL * * *
"The purpose of this notification is to retract the 10 CFR 50.72(b)(3)(v)(D) reporting criteria of event notification 57046 reported on March 23,2024. Based on further evaluation, Fermi 2 has concluded that there was no event or condition that could have prevented fulfillment of a safety function that was needed to mitigate the consequence of an accident. Although discussed in Chapter 15 of the UFSAR, the turbine bypass valves do not provide a safety related function and are not credited safety related components for accident mitigation. Therefore, Fermi 2 is retracting the 10 CFR 50.72(b)(3)(v)(D) reporting criteria that was included on the March 23, 2024 event notification."
Notified R3DO (Betancourt-Roldan)
EN Revision Text: AUTOMATIC REACTOR TRIP
The following information was provided by the licensee via email:
"At 0004 EDT on March 23, 2024, with the unit in Mode 1 at 23 percent power, the reactor automatically scrammed due to high reactor pressure vessel pressure when the turbine bypass valves unexpectedly closed while attempting to lower generator MW to 55 MWe to support shutdown for a refueling outage. The scram was not complex, with systems responding normally post-scram, with the exception of the pressure control system. The transient occurred while lowering on turbine speed/load demand which caused a rise in pressure and power until the reactor protection system setpoint for reactor pressure high was exceeded and resulted in an automatic reactor scram. The plant was preparing to shut down for a refueling outage when the trip occurred.
"Operations responded and stabilized the plant. Reactor water level is being maintained at normal level. Decay heat is being removed by the main steam system to the main condenser using manual operation of the turbine bypass valves. All control rods inserted into the core.
"Due to the reactor protection system actuation while critical, this event is being reported as a four-hour, non-emergency notification per 10 CPR 50.72(b)(2)(iv)(B). Additionally, received expected [primary containment] isolations for Level 3: Group 13 drywell sumps, Group 15 [traverse in-core probe] TlPs (which was already isolated) and Group 4 [residual heat removal - shutdown cooling] RHR-SDC (which was already isolated). The primary containment isolation event is being reported under 10 CFR 50.72(b)(3)(iv)(A). Also, due to the main turbine bypass valves unexpectedly closing, this is also being reported under 10 CFR 50.72(b)(3)(v)(D).
"There was no impact to the health and safety of the public or plant personnel. The NRC Resident Inspector has been notified."
* * * UPDATE ON 4/22/24 AT 1448 EDT FROM WHITNEY HEMINGWAY TO ADAM KOZIOL * * *
"The purpose of this notification is to retract the 10 CFR 50.72(b)(3)(v)(D) reporting criteria of event notification 57046 reported on March 23,2024. Based on further evaluation, Fermi 2 has concluded that there was no event or condition that could have prevented fulfillment of a safety function that was needed to mitigate the consequence of an accident. Although discussed in Chapter 15 of the UFSAR, the turbine bypass valves do not provide a safety related function and are not credited safety related components for accident mitigation. Therefore, Fermi 2 is retracting the 10 CFR 50.72(b)(3)(v)(D) reporting criteria that was included on the March 23, 2024 event notification."
Notified R3DO (Betancourt-Roldan)
Agreement State
Event Number: 57078
Rep Org: California Radiation Control Prgm
Licensee: Testing Engineers, Inc.
Region: 4
City: Concord State: CA
County:
License #: 3691-07
Agreement: Y
Docket:
NRC Notified By: K. Arunika Hewadikaram
HQ OPS Officer: Ernest West
Licensee: Testing Engineers, Inc.
Region: 4
City: Concord State: CA
County:
License #: 3691-07
Agreement: Y
Docket:
NRC Notified By: K. Arunika Hewadikaram
HQ OPS Officer: Ernest West
Notification Date: 04/16/2024
Notification Time: 15:57 [ET]
Event Date: 04/13/2024
Event Time: 00:00 [PDT]
Last Update Date: 04/16/2024
Notification Time: 15:57 [ET]
Event Date: 04/13/2024
Event Time: 00:00 [PDT]
Last Update Date: 04/16/2024
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
10 CFR Section:
Agreement State
Person (Organization):
Young, Cale (R4DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
ILTAB, (EMAIL) (EMAIL)
CNSNS (Mexico), - (EMAIL)
Young, Cale (R4DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
ILTAB, (EMAIL) (EMAIL)
CNSNS (Mexico), - (EMAIL)
AGREEMENT STATE - STOLEN GAUGE
The following information was provided by the California Department of Public Health, Radiologic Health Branch (RHB) via email:
"On 4/15/2024, the California Office of Emergency Services (OES) forwarded a report from Testing Engineers, Inc. The radiation safety officer (RSO) notified OES that one of their nuclear gauges (CPN MC-1, serial number MD71108870 containing 10 mCi of Cs-137 and 50 mCi of Am-241) was stolen from a storage unit that is located within a public storage facility in Concord, CA. The gauge was stolen from the storage unit at an unknown time between 04/13/2024 and 04/14/2024, but was discovered missing at 1541 [PDT] on 04/15/2024. A car was used to ram the door of the storage unit, and a pry bar was used to remove the gauge from a locked cabinet. Local law enforcement was notified, and a reward was posted on Craigslist, Facebook, and Nextdoor for the safe return of the gauge.
"RHB will investigate the incident."
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
The following information was provided by the California Department of Public Health, Radiologic Health Branch (RHB) via email:
"On 4/15/2024, the California Office of Emergency Services (OES) forwarded a report from Testing Engineers, Inc. The radiation safety officer (RSO) notified OES that one of their nuclear gauges (CPN MC-1, serial number MD71108870 containing 10 mCi of Cs-137 and 50 mCi of Am-241) was stolen from a storage unit that is located within a public storage facility in Concord, CA. The gauge was stolen from the storage unit at an unknown time between 04/13/2024 and 04/14/2024, but was discovered missing at 1541 [PDT] on 04/15/2024. A car was used to ram the door of the storage unit, and a pry bar was used to remove the gauge from a locked cabinet. Local law enforcement was notified, and a reward was posted on Craigslist, Facebook, and Nextdoor for the safe return of the gauge.
"RHB will investigate the incident."
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
Part 21
Event Number: 57088
Rep Org: Global Nuclear Fuel
Licensee: GE-Hitachi Nuclear Energy Americas, LLC
Region: 2
City: Wilmington State: NC
County:
License #: SNM-1097
Agreement: Y
Docket:
NRC Notified By: Ralph Hayes
HQ OPS Officer: Adam Koziol
Licensee: GE-Hitachi Nuclear Energy Americas, LLC
Region: 2
City: Wilmington State: NC
County:
License #: SNM-1097
Agreement: Y
Docket:
NRC Notified By: Ralph Hayes
HQ OPS Officer: Adam Koziol
Notification Date: 04/22/2024
Notification Time: 14:33 [ET]
Event Date: 04/22/2024
Event Time: 00:00 [EDT]
Last Update Date: 04/26/2024
Notification Time: 14:33 [ET]
Event Date: 04/22/2024
Event Time: 00:00 [EDT]
Last Update Date: 04/26/2024
Emergency Class: Non Emergency
10 CFR Section:
21.21(d)(3)(i) - Defects And Noncompliance
10 CFR Section:
21.21(d)(3)(i) - Defects And Noncompliance
Person (Organization):
Werkheiser, Dave (R1DO)
Part 21/50.55 Reactors, - (EMAIL)
Betancourt-Roldan, Diana (R3DO)
Warnick, Greg (R4DO)
Werkheiser, Dave (R1DO)
Part 21/50.55 Reactors, - (EMAIL)
Betancourt-Roldan, Diana (R3DO)
Warnick, Greg (R4DO)
EN Revision Imported Date: 4/29/2024
EN Revision Text: PART 21 - FUEL ASSEMBLY SPACER RELOCATION
The following is a summary of information provided by the licensee via email:
Global Nuclear Fuel discovered instances of GNF3 fuel assembly spacers relocating within the fuel bundle. A safety communication was issued in 2022 following the discovery of a raised water rod (WR) at Grand Gulf Nuclear Station. Shutdown inspections in February 2024 at Lasalle identified five spacers out of position. Shutdown inspections at Limerick in April 2024 identified one spacer out of position. Those discoveries prompted this Part 21 report. An evaluation concluded that the relocated spacers could result in a degraded critical power margin, but the evaluation of this condition indicates it will not compromise or greatly reduce protection to public health and safety.
Plants with suspect bundles installed:
Grand Gulf Nuclear Station (Raised WR but no defective spacers)
Lasalle (1 bundle with 5 relocated spacers found)
Limerick (1 bundle with 4 relocated spacers found)
Nine Mile Point (No defects found)
Fermi (No defects found)
Peach Bottom (Shutdown scheduled in Fall 2024)
Fitzpatrick (Shutdown scheduled in Fall 2024)
* * * UPDATE ON 4/26/24 AT 1220 EDT FROM LISA SCHICHLEIN TO ADAM KOZIOL * * *
Updated to correct administrative errors in the summary of defects. Corrections were made above.
Notified R1DO (Werkheiser), R3DO (Betancourt-Roldan), R4DO (Warnick), Part 21/Reactor Group (email)
EN Revision Text: PART 21 - FUEL ASSEMBLY SPACER RELOCATION
The following is a summary of information provided by the licensee via email:
Global Nuclear Fuel discovered instances of GNF3 fuel assembly spacers relocating within the fuel bundle. A safety communication was issued in 2022 following the discovery of a raised water rod (WR) at Grand Gulf Nuclear Station. Shutdown inspections in February 2024 at Lasalle identified five spacers out of position. Shutdown inspections at Limerick in April 2024 identified one spacer out of position. Those discoveries prompted this Part 21 report. An evaluation concluded that the relocated spacers could result in a degraded critical power margin, but the evaluation of this condition indicates it will not compromise or greatly reduce protection to public health and safety.
Plants with suspect bundles installed:
Grand Gulf Nuclear Station (Raised WR but no defective spacers)
Lasalle (1 bundle with 5 relocated spacers found)
Limerick (1 bundle with 4 relocated spacers found)
Nine Mile Point (No defects found)
Fermi (No defects found)
Peach Bottom (Shutdown scheduled in Fall 2024)
Fitzpatrick (Shutdown scheduled in Fall 2024)
* * * UPDATE ON 4/26/24 AT 1220 EDT FROM LISA SCHICHLEIN TO ADAM KOZIOL * * *
Updated to correct administrative errors in the summary of defects. Corrections were made above.
Notified R1DO (Werkheiser), R3DO (Betancourt-Roldan), R4DO (Warnick), Part 21/Reactor Group (email)