Event Notification Report for March 10, 2024

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
03/09/2024 - 03/10/2024

EVENT NUMBERS
57019
Power Reactor
Event Number: 57019
Facility: South Texas
Region: 4     State: TX
Unit: [1] [] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: Billy Herzog
HQ OPS Officer: Brian P. Smith
Notification Date: 03/10/2024
Notification Time: 12:05 [ET]
Event Date: 03/10/2024
Event Time: 03:53 [CDT]
Last Update Date: 03/10/2024
Emergency Class: Non Emergency
10 CFR Section:
50.72(b)(3)(v)(D) - Accident Mitigation
Person (Organization):
Gaddy, Vincent (R4DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
ESSENTIAL CHILLED WATER TRAINS DECLARED INOPERABLE

The following information was provided by the licensee via email:

"On 3/9/2024 at 2126 CST, train C essential cooling water was declared inoperable due to a through-wall leak on the discharge vent line. This would also cascade and cause train C essential chilled water to be inoperable.

"On 3/10/2024 at 0353 CDT, train B essential chilled water was declared inoperable due to chilled water outlet temperature greater than 52 degrees F following startup of essential chiller 12B. Chilled water outlet temperature was adjusted to less than 52 degrees F at 0440 CDT, and train B essential chilled water was declared operable.

"This condition resulted in the inoperability of two of the three safety trains required for the accident mitigating functions including: high head safety injection, low head safety injection, containment spray, electrical auxiliary building HVAC, control room envelope HVAC, and essential chilled water.

"This is an 8 hour reportable condition per 10CFR50.72(b)(3)(v)(D) because it could affect the ability to mitigate the consequences of an accident."

The licensee notified the NRC Resident Inspector.