Event Notification Report for January 29, 2024
U.S. Nuclear Regulatory Commission
Operations Center
EVENT REPORTS FOR
01/28/2024 - 01/29/2024
Agreement State
Event Number: 56895
Rep Org: Illinois Emergency Mgmt. Agency
Licensee: Sterigenics U.S. LLC
Region: 3
City: Gurnee State: IL
County:
License #: IL-01220-01
Agreement: Y
Docket:
NRC Notified By: Gary Foresee
HQ OPS Officer: Brian Lin
Licensee: Sterigenics U.S. LLC
Region: 3
City: Gurnee State: IL
County:
License #: IL-01220-01
Agreement: Y
Docket:
NRC Notified By: Gary Foresee
HQ OPS Officer: Brian Lin
Notification Date: 12/17/2023
Notification Time: 21:31 [ET]
Event Date: 12/16/2023
Event Time: 23:00 [CST]
Last Update Date: 01/26/2024
Notification Time: 21:31 [ET]
Event Date: 12/16/2023
Event Time: 23:00 [CST]
Last Update Date: 01/26/2024
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
10 CFR Section:
Agreement State
Person (Organization):
McCraw, Aaron (R3DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
McCraw, Aaron (R3DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
EN Revision Imported Date: 1/29/2024
EN Revision Text: AGREEMENT STATE REPORT - STUCK SOURCE RACK
The following information was received from the Illinois Emergency Management Agency (IEMA-OHS) via email:
"The IEMA-OHS Operations Center was contacted at 1712 CDT on December 17, 2023, by the radiation safety officer for Sterigenics to report a stuck source rack. The rack reportedly became stuck around 2300 on December 16, 2023, with approximately 10 percent of the sources above the pool level. The area was isolated with an additional restricted area established to maintain occupational exposures within limits. At this time, no public or occupational exposures above regulatory limits have been reported. This matter has a 24-hour reporting requirement under 32 Ill. Adm. Code 346.830 which was met by the licensee. IEMA-OHS inspectors will arrive at the facility on 12/18 to evaluate timelines for corrective action and the efficacy of safety systems. Staff will also evaluate the site and review staff dosimetry, potential impacts to source capsule integrity, any anticipated heat impacts, and plans for quality assurance of the impacted system(s)."
Source type: sealed source irradiator
Radionuclide: Co-60
Activity: 24 MCi (888 PBq)
Model no.: C-188
Illinois report no.: IL230036
* * * UPDATE ON 12/19/23 FROM WHITNEY COX TO DAN LIVERMORE * * *
The following information was received from the Illinois Emergency Management Agency (IEMA-OHS) via email:
"Agency staff arrived at the site on 12/18/23 and surveys indicate no public or occupational exposure levels above normal operation. The source rack is still stuck in the unshielded position. The Agency continues to monitor the situation and will update when additional information is available."
Notified R3DO (Edwards), NMSS (via email).
* * * UPDATE ON 1/4/24 FROM GARY FORSEE TO IAN HOWARD * * *
The following information was received from the Illinois Emergency Management Agency (IEMA-OHS) via email:
"The Licensee reports 18 modules (3 rows), constituting 626,000 curies of Co-60, in the B/C cell remain stuck in the unshielded position due to product carts impeding travel of the rack. The sources are below the point of product cart impact. A second IEMA-OHS inspection was conducted to increase coordination on response activities and obtain additional data on the following: security requirements (all operational), radiation levels (700 microR/hour maximum reading), dosimetry procedures (transitioned to digital dosimetry which is read daily and employed at a 40 mrem/day investigational level), total occupational doses to date (20 mrem), exposure rate maps including access points used for radiation hardened cameras, personnel access, pool conductivity (within specifications), updated operations and emergency procedures (confirmed), on site staff and safety culture (satisfactory, additional manufacturer health physics staff brought in to assist), fire hazards (none at this time), status of deionizer (satisfactory), and mitigation planning.
"The Licensee is awaiting cameras and remote vehicles capable of withstanding radiation levels and manipulating product totes. The facility was confirmed to be in a safe and stable condition and ongoing response operations will be coordinated with IEMA-OHS. IEMA-OHS has now transitioned to weekly inspections until the incident is remedied.
"Updates will be provided as they become available."
Notified R3DO (Stoedter), NMSS (via email).
* * * UPDATE ON 01/26/24 FROM GARY FORSEE TO THOMAS HERRITY * * *
The following information was received from the Illinois Emergency Management Agency (IEMA-OHS) via email:
"The source rack was successfully returned to the shielded position. Sterigenics staff employed engineered tooling to access the stuck rack through roof projections on the evening of 1/25/24. IEMA-OHS staff were on site to observe setup and operations throughout the week. A review of digital dosimetry in use for all phases of the operations indicates there were no occupational exposures in excess of regulatory limits.
"Full report and root cause analysis pending. This report will be updated."
Notified R3DO (Orlikowski), NMSS (via email).
EN Revision Text: AGREEMENT STATE REPORT - STUCK SOURCE RACK
The following information was received from the Illinois Emergency Management Agency (IEMA-OHS) via email:
"The IEMA-OHS Operations Center was contacted at 1712 CDT on December 17, 2023, by the radiation safety officer for Sterigenics to report a stuck source rack. The rack reportedly became stuck around 2300 on December 16, 2023, with approximately 10 percent of the sources above the pool level. The area was isolated with an additional restricted area established to maintain occupational exposures within limits. At this time, no public or occupational exposures above regulatory limits have been reported. This matter has a 24-hour reporting requirement under 32 Ill. Adm. Code 346.830 which was met by the licensee. IEMA-OHS inspectors will arrive at the facility on 12/18 to evaluate timelines for corrective action and the efficacy of safety systems. Staff will also evaluate the site and review staff dosimetry, potential impacts to source capsule integrity, any anticipated heat impacts, and plans for quality assurance of the impacted system(s)."
Source type: sealed source irradiator
Radionuclide: Co-60
Activity: 24 MCi (888 PBq)
Model no.: C-188
Illinois report no.: IL230036
* * * UPDATE ON 12/19/23 FROM WHITNEY COX TO DAN LIVERMORE * * *
The following information was received from the Illinois Emergency Management Agency (IEMA-OHS) via email:
"Agency staff arrived at the site on 12/18/23 and surveys indicate no public or occupational exposure levels above normal operation. The source rack is still stuck in the unshielded position. The Agency continues to monitor the situation and will update when additional information is available."
Notified R3DO (Edwards), NMSS (via email).
* * * UPDATE ON 1/4/24 FROM GARY FORSEE TO IAN HOWARD * * *
The following information was received from the Illinois Emergency Management Agency (IEMA-OHS) via email:
"The Licensee reports 18 modules (3 rows), constituting 626,000 curies of Co-60, in the B/C cell remain stuck in the unshielded position due to product carts impeding travel of the rack. The sources are below the point of product cart impact. A second IEMA-OHS inspection was conducted to increase coordination on response activities and obtain additional data on the following: security requirements (all operational), radiation levels (700 microR/hour maximum reading), dosimetry procedures (transitioned to digital dosimetry which is read daily and employed at a 40 mrem/day investigational level), total occupational doses to date (20 mrem), exposure rate maps including access points used for radiation hardened cameras, personnel access, pool conductivity (within specifications), updated operations and emergency procedures (confirmed), on site staff and safety culture (satisfactory, additional manufacturer health physics staff brought in to assist), fire hazards (none at this time), status of deionizer (satisfactory), and mitigation planning.
"The Licensee is awaiting cameras and remote vehicles capable of withstanding radiation levels and manipulating product totes. The facility was confirmed to be in a safe and stable condition and ongoing response operations will be coordinated with IEMA-OHS. IEMA-OHS has now transitioned to weekly inspections until the incident is remedied.
"Updates will be provided as they become available."
Notified R3DO (Stoedter), NMSS (via email).
* * * UPDATE ON 01/26/24 FROM GARY FORSEE TO THOMAS HERRITY * * *
The following information was received from the Illinois Emergency Management Agency (IEMA-OHS) via email:
"The source rack was successfully returned to the shielded position. Sterigenics staff employed engineered tooling to access the stuck rack through roof projections on the evening of 1/25/24. IEMA-OHS staff were on site to observe setup and operations throughout the week. A review of digital dosimetry in use for all phases of the operations indicates there were no occupational exposures in excess of regulatory limits.
"Full report and root cause analysis pending. This report will be updated."
Notified R3DO (Orlikowski), NMSS (via email).
Agreement State
Event Number: 56929
Rep Org: Maine Radiation Control Program
Licensee: NETCO
Region: 1
City: Windsor State: ME
County:
License #: ME 11613
Agreement: Y
Docket:
NRC Notified By: James Nizamoff
HQ OPS Officer: Brian P. Smith
Licensee: NETCO
Region: 1
City: Windsor State: ME
County:
License #: ME 11613
Agreement: Y
Docket:
NRC Notified By: James Nizamoff
HQ OPS Officer: Brian P. Smith
Notification Date: 01/19/2024
Notification Time: 12:53 [ET]
Event Date: 12/22/2023
Event Time: 00:00 [EST]
Last Update Date: 01/19/2024
Notification Time: 12:53 [ET]
Event Date: 12/22/2023
Event Time: 00:00 [EST]
Last Update Date: 01/19/2024
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
10 CFR Section:
Agreement State
Person (Organization):
Lally, Christopher (R1DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
ILTAB, (EMAIL) (EMAIL)
CNSC (Canada) (EMAIL)
Lally, Christopher (R1DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
ILTAB, (EMAIL) (EMAIL)
CNSC (Canada) (EMAIL)
AGREEMENT STATE REPORT - LOST SOURCE
The following report in part was received via email from the Maine Radiological Control Program [MRCP]:
"The licensee service manager contacted MRCP by phone on December 22, 2023, to report that a source could not be accounted for during a monthly source inventory. The service manager reported that the missing source had been observed in the service area of the licensee's facility in Windsor, ME, approximately two weeks before the inventory identified it as missing. The missing source had been removed from a customer's machine and replaced with a new source. The missing source is an 8 mCi Ni-63 source with serial number 09-6700 from Isotope Products Laboratories, Valencia, CA. The source was still in its sealed form inside the detector housing which is assembled with tamper-proof screws. Once the source was determined unaccounted for in the monthly inventory, a team of licensee employees searched the entire facility, spending in excess of 20 man-hours trying to locate it. The licensee's best assumption is that the missing source may have been accidentally disposed of during a recent shop cleaning. MRCP conducted a site inspection on January 2, 2024, to gather information regarding the incident. A licensee service technician was able to trace the waste stream which is routinely deposited in a dumpster and is then transported to the Waterville, ME, transfer station. As of January 19, 2024, the missing Ni-63 source remains lost."
Maine Event Report Number: ME 2023-002
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
The following report in part was received via email from the Maine Radiological Control Program [MRCP]:
"The licensee service manager contacted MRCP by phone on December 22, 2023, to report that a source could not be accounted for during a monthly source inventory. The service manager reported that the missing source had been observed in the service area of the licensee's facility in Windsor, ME, approximately two weeks before the inventory identified it as missing. The missing source had been removed from a customer's machine and replaced with a new source. The missing source is an 8 mCi Ni-63 source with serial number 09-6700 from Isotope Products Laboratories, Valencia, CA. The source was still in its sealed form inside the detector housing which is assembled with tamper-proof screws. Once the source was determined unaccounted for in the monthly inventory, a team of licensee employees searched the entire facility, spending in excess of 20 man-hours trying to locate it. The licensee's best assumption is that the missing source may have been accidentally disposed of during a recent shop cleaning. MRCP conducted a site inspection on January 2, 2024, to gather information regarding the incident. A licensee service technician was able to trace the waste stream which is routinely deposited in a dumpster and is then transported to the Waterville, ME, transfer station. As of January 19, 2024, the missing Ni-63 source remains lost."
Maine Event Report Number: ME 2023-002
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
Agreement State
Event Number: 56930
Rep Org: WA Office of Radiation Protection
Licensee: Swedish Medical Center
Region: 4
City: Seattle State: WA
County:
License #: WN-M008
Agreement: Y
Docket:
NRC Notified By: Boris Tsenov
HQ OPS Officer: Brian P. Smith
Licensee: Swedish Medical Center
Region: 4
City: Seattle State: WA
County:
License #: WN-M008
Agreement: Y
Docket:
NRC Notified By: Boris Tsenov
HQ OPS Officer: Brian P. Smith
Notification Date: 01/22/2024
Notification Time: 18:11 [ET]
Event Date: 01/19/2024
Event Time: 12:00 [PST]
Last Update Date: 01/31/2024
Notification Time: 18:11 [ET]
Event Date: 01/19/2024
Event Time: 12:00 [PST]
Last Update Date: 01/31/2024
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
10 CFR Section:
Agreement State
Person (Organization):
O'Keefe, Neil (R4DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
O'Keefe, Neil (R4DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
EN Revision Imported Date: 2/1/2024
EN Revision Text: AGREEMENT STATE REPORT - Y-90 MICROSPHERE MISADMINISTRATION
The following is a summary of information received via email from the Washington Office of Radiation Protection:
On the afternoon of Friday, January 19th, a Pluvicto (radiopharmaceutical) dose was not administered properly. A typical administered dose may have up to 2 to 4 mCi of residual activity after a 200 mCi administration. However, for this administration there was 43 mCi of residual activity and only 149 mCi of calculated administered activity for a 200 mCi prescribed dose. Pluvicto is a six fraction, six administration regimen with about six weeks between each administration, and this was the patient's fourth fractional dose. Treated as a single administration treatment, this constitutes a medical event as the dose administered activity of 149 mCi is more than 20% less than the 200 mCi prescribed dose. The final report will be sent in 15 days.
Washington Event Number: WA-24-003
A Medical Event may indicate potential problems in a medical facility's use of radioactive materials. It does not necessarily result in harm to the patient.
* * * UPDATE ON 1/29/2024 AT 1401 EST FROM BORIS TSENOV TO NATALIE STARFISH * * *
The following information is a synopsis of information provided by the Washington State Radioactive Materials Section:
A lutetium 177 (drug name: Pluvicto) dose was prescribed to be 200 mCi. The calculated dose administered to the patient was about 149 mCi, based upon the measured residual. The underdosing occurred due to a method of folding and crimping the intravenous tube with a hemostat and gauze instead of utilizing the kit provided clamp. The hospital supply chain of the intravenous kit was recently changed and the needed clamp was thought to be missing. To prevent future crimping of the intravenous tube, the use of hemostat and gauze will no longer be used.
This dose was the fourth dose of six prescribed to the patient, with six weeks between each administration. There is no expected change in the patient's treatment or prognosis based on the underdosing of the fourth fraction of six and no additional actions are required.
Final report will be sent in 15 days.
Washington Event Number: WA-24-003
A Medical Event may indicate potential problems in a medical facility's use of radioactive materials. It does not necessarily result in harm to the patient.
Notified R4DO (Agrawal) and NMSS (email).
EN Revision Text: AGREEMENT STATE REPORT - Y-90 MICROSPHERE MISADMINISTRATION
The following is a summary of information received via email from the Washington Office of Radiation Protection:
On the afternoon of Friday, January 19th, a Pluvicto (radiopharmaceutical) dose was not administered properly. A typical administered dose may have up to 2 to 4 mCi of residual activity after a 200 mCi administration. However, for this administration there was 43 mCi of residual activity and only 149 mCi of calculated administered activity for a 200 mCi prescribed dose. Pluvicto is a six fraction, six administration regimen with about six weeks between each administration, and this was the patient's fourth fractional dose. Treated as a single administration treatment, this constitutes a medical event as the dose administered activity of 149 mCi is more than 20% less than the 200 mCi prescribed dose. The final report will be sent in 15 days.
Washington Event Number: WA-24-003
A Medical Event may indicate potential problems in a medical facility's use of radioactive materials. It does not necessarily result in harm to the patient.
* * * UPDATE ON 1/29/2024 AT 1401 EST FROM BORIS TSENOV TO NATALIE STARFISH * * *
The following information is a synopsis of information provided by the Washington State Radioactive Materials Section:
A lutetium 177 (drug name: Pluvicto) dose was prescribed to be 200 mCi. The calculated dose administered to the patient was about 149 mCi, based upon the measured residual. The underdosing occurred due to a method of folding and crimping the intravenous tube with a hemostat and gauze instead of utilizing the kit provided clamp. The hospital supply chain of the intravenous kit was recently changed and the needed clamp was thought to be missing. To prevent future crimping of the intravenous tube, the use of hemostat and gauze will no longer be used.
This dose was the fourth dose of six prescribed to the patient, with six weeks between each administration. There is no expected change in the patient's treatment or prognosis based on the underdosing of the fourth fraction of six and no additional actions are required.
Final report will be sent in 15 days.
Washington Event Number: WA-24-003
A Medical Event may indicate potential problems in a medical facility's use of radioactive materials. It does not necessarily result in harm to the patient.
Notified R4DO (Agrawal) and NMSS (email).
Power Reactor
Event Number: 56935
Facility: Watts Bar
Region: 2 State: TN
Unit: [2] [] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: Ryan Nessell
HQ OPS Officer: Bill Gott
Region: 2 State: TN
Unit: [2] [] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: Ryan Nessell
HQ OPS Officer: Bill Gott
Notification Date: 01/27/2024
Notification Time: 23:39 [ET]
Event Date: 01/27/2024
Event Time: 21:41 [EST]
Last Update Date: 01/27/2024
Notification Time: 23:39 [ET]
Event Date: 01/27/2024
Event Time: 21:41 [EST]
Last Update Date: 01/27/2024
Emergency Class: Non Emergency
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS Actuation - Critical 50.72(b)(3)(iv)(A) - Valid Specif Sys Actuation
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS Actuation - Critical 50.72(b)(3)(iv)(A) - Valid Specif Sys Actuation
Person (Organization):
Miller, Mark (R2DO)
Miller, Mark (R2DO)
Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
---|---|---|---|---|---|---|
2 | A/R | Y | 100 | Power Operation | 0 | Hot Standby |
AUTOMATIC REACTOR TRIP
The following information was provided by the licensee via email:
"At 2141 EDT, with Unit 2 in Mode 1 at 100 percent power, the reactor automatically tripped due to a main turbine trip. The trip was not complex, with all systems responding normally post-trip.
"Operations responded and stabilized the plant. Decay heat is being removed using the auxiliary feedwater and steam dump systems. Unit 1 is not affected.
"Due to the reactor protection system actuation while critical, this event is being reported as a four-hour, non-emergency notification per 10 CFR 50.72(b)(2)(iv)(B). The expected actuation of the auxiliary feedwater system (an engineered safety feature) is being reported as an eight hour report under 10 CFR 50.72(b)(3)(iv)(A).
"There was no impact on the health and safety of the public or plant personnel. The NRC Resident Inspector has been notified.
"All control rods are fully inserted. The cause of the turbine trip is being investigated."
The licensee notified the NRC Resident Inspector.
The following information was provided by the licensee via email:
"At 2141 EDT, with Unit 2 in Mode 1 at 100 percent power, the reactor automatically tripped due to a main turbine trip. The trip was not complex, with all systems responding normally post-trip.
"Operations responded and stabilized the plant. Decay heat is being removed using the auxiliary feedwater and steam dump systems. Unit 1 is not affected.
"Due to the reactor protection system actuation while critical, this event is being reported as a four-hour, non-emergency notification per 10 CFR 50.72(b)(2)(iv)(B). The expected actuation of the auxiliary feedwater system (an engineered safety feature) is being reported as an eight hour report under 10 CFR 50.72(b)(3)(iv)(A).
"There was no impact on the health and safety of the public or plant personnel. The NRC Resident Inspector has been notified.
"All control rods are fully inserted. The cause of the turbine trip is being investigated."
The licensee notified the NRC Resident Inspector.
Agreement State
Event Number: 56931
Rep Org: Louisiana Radiation Protection Div
Licensee: Louisiana Scrap Metal Recycling
Region: 4
City: Gibson State: LA
County:
License #: Unknown
Agreement: Y
Docket:
NRC Notified By: Russell Clark
HQ OPS Officer: Ernest West
Licensee: Louisiana Scrap Metal Recycling
Region: 4
City: Gibson State: LA
County:
License #: Unknown
Agreement: Y
Docket:
NRC Notified By: Russell Clark
HQ OPS Officer: Ernest West
Notification Date: 01/23/2024
Notification Time: 18:07 [ET]
Event Date: 01/22/2024
Event Time: 14:00 [CST]
Last Update Date: 01/23/2024
Notification Time: 18:07 [ET]
Event Date: 01/22/2024
Event Time: 14:00 [CST]
Last Update Date: 01/23/2024
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
10 CFR Section:
Agreement State
Person (Organization):
O'Keefe, Neil (R4DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
O'Keefe, Neil (R4DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
TWO SUSPECTED ORPHAN GAUGES FOUND
The following information was provided by the Louisiana Department of Environmental Quality (LDEQ) via email:
"On January 22, 2024, at approximately 1400, Central Standard Time (CST), an unidentified nuclear gauge of roughly cylindrical dimensions and less than 30 cm in length and 12 cm in width was detected by the entrance gate radiation monitor at the Louisiana Scrap Metal facility (LA Scrap) located in Gibson, LA in Terrebonne Parish. Facility scrap surveyors were immediately dispatched to more close survey the suspected gauge using Ludlum Model 3 survey instruments with external probes. During this time an additional suspected nuclear gauge, similar in design and overall dimensions to the first, was discovered by the facility's scrap surveyors. Surface radiation readings of approximately 0.9 to 1.2 mR/hr were observed at the surface of both devices. No identifying markings, labels or tags were noted on the gauges' surfaces, and both devices appeared to have sustained significant corrosion to their housings, which nonetheless appeared intact. The devices were believed by the reporting party to have originated with scrap from the disassembly of a 220-foot marine vessel purchased by LA Scrap from a Florida scrap broker. The above incident was reported via the LDEQ Radiation Hotline at approximately 1335 CST on January 23, 2024. The facility is awaiting identification of the devices' isotope(s) (to be provided by the LDEQ) prior to contracting with BBP Sales, Louisiana Radioactive Material License, LA-10799-L01, for inspection, leak testing, packaging, and disposal of the devices.
"The facility environmental health and safety (EHS) manager, stated that the gauges have been enclosed in a bucket of moist dirt and secured within an area on site with restricted access. Facility workers were advised by the EHS manager to stay clear of the area in the meantime."
LA Event Report ID: LA240002
The following information was provided by the Louisiana Department of Environmental Quality (LDEQ) via email:
"On January 22, 2024, at approximately 1400, Central Standard Time (CST), an unidentified nuclear gauge of roughly cylindrical dimensions and less than 30 cm in length and 12 cm in width was detected by the entrance gate radiation monitor at the Louisiana Scrap Metal facility (LA Scrap) located in Gibson, LA in Terrebonne Parish. Facility scrap surveyors were immediately dispatched to more close survey the suspected gauge using Ludlum Model 3 survey instruments with external probes. During this time an additional suspected nuclear gauge, similar in design and overall dimensions to the first, was discovered by the facility's scrap surveyors. Surface radiation readings of approximately 0.9 to 1.2 mR/hr were observed at the surface of both devices. No identifying markings, labels or tags were noted on the gauges' surfaces, and both devices appeared to have sustained significant corrosion to their housings, which nonetheless appeared intact. The devices were believed by the reporting party to have originated with scrap from the disassembly of a 220-foot marine vessel purchased by LA Scrap from a Florida scrap broker. The above incident was reported via the LDEQ Radiation Hotline at approximately 1335 CST on January 23, 2024. The facility is awaiting identification of the devices' isotope(s) (to be provided by the LDEQ) prior to contracting with BBP Sales, Louisiana Radioactive Material License, LA-10799-L01, for inspection, leak testing, packaging, and disposal of the devices.
"The facility environmental health and safety (EHS) manager, stated that the gauges have been enclosed in a bucket of moist dirt and secured within an area on site with restricted access. Facility workers were advised by the EHS manager to stay clear of the area in the meantime."
LA Event Report ID: LA240002
Agreement State
Event Number: 56932
Rep Org: California Radiation Control Prgm
Licensee: TRC Engineers Inc.
Region: 4
City: Santa Clara State: CA
County:
License #: 2536-43
Agreement: Y
Docket:
NRC Notified By: K. Arunika Hewadikaram
HQ OPS Officer: Karen Cotton-Gross
Licensee: TRC Engineers Inc.
Region: 4
City: Santa Clara State: CA
County:
License #: 2536-43
Agreement: Y
Docket:
NRC Notified By: K. Arunika Hewadikaram
HQ OPS Officer: Karen Cotton-Gross
Notification Date: 01/23/2024
Notification Time: 20:20 [ET]
Event Date: 01/22/2024
Event Time: 22:00 [PST]
Last Update Date: 01/23/2024
Notification Time: 20:20 [ET]
Event Date: 01/22/2024
Event Time: 22:00 [PST]
Last Update Date: 01/23/2024
Emergency Class: Non Emergency
10 CFR Section:
Agreement State
10 CFR Section:
Agreement State
Person (Organization):
O'Keefe, Neil (R4DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
ILTAB, (EMAIL) (EMAIL)
CNSNS (Mexico), - (EMAIL)
O'Keefe, Neil (R4DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
ILTAB, (EMAIL) (EMAIL)
CNSNS (Mexico), - (EMAIL)
AGREEMENT STATE REPORT - STOLEN MOISTURE DENSITY GAUGE
The following information was provided by the California Department of Public Health Radiologic Health Branch (RHB) via email:
"On 1/23/24, California Governor's Office of Emergency Services (CAL OES), contacted RHB to report a stolen moisture density gauge. Per the CAL OES report, at around 2200 PST on 01/22/24, a portable gauge was stolen from the bed of a parked truck belonging to the reporting party.
"On 1/23/24, RHB contacted the reporting party (gauge user) and learned the following:
"The stolen gauge is a CPN Model 131, serial number, MD 00705803, containing 10 mCi of Cs-137 and 50 mCi of Am-241. On 1/22/24, around 2030 PST, the gauge user was feeling ill and was not able to return the gauge to the storage unit and decided to leave it in his work truck parked at his residence. On the next day morning (1/23/24) at around 0700, the user drove his truck to a job site in Palo Alto, CA, opened the cover of the bed of the truck and discovered that the gauge was stolen from the vehicle. There were no signs of a break-in, so the truck bed may have been left unlocked. The gauge storage box was chained through two handles and was attached to the bed of the truck. On 1/23/24, at around 1400 PST, the gauge user notified the Daily City Police Department of the stolen gauge (Report No. T24000071).
"RHB will be following up on this investigation."
CAL OES Report CENTRL No.: 24-0397
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
The following information was provided by the California Department of Public Health Radiologic Health Branch (RHB) via email:
"On 1/23/24, California Governor's Office of Emergency Services (CAL OES), contacted RHB to report a stolen moisture density gauge. Per the CAL OES report, at around 2200 PST on 01/22/24, a portable gauge was stolen from the bed of a parked truck belonging to the reporting party.
"On 1/23/24, RHB contacted the reporting party (gauge user) and learned the following:
"The stolen gauge is a CPN Model 131, serial number, MD 00705803, containing 10 mCi of Cs-137 and 50 mCi of Am-241. On 1/22/24, around 2030 PST, the gauge user was feeling ill and was not able to return the gauge to the storage unit and decided to leave it in his work truck parked at his residence. On the next day morning (1/23/24) at around 0700, the user drove his truck to a job site in Palo Alto, CA, opened the cover of the bed of the truck and discovered that the gauge was stolen from the vehicle. There were no signs of a break-in, so the truck bed may have been left unlocked. The gauge storage box was chained through two handles and was attached to the bed of the truck. On 1/23/24, at around 1400 PST, the gauge user notified the Daily City Police Department of the stolen gauge (Report No. T24000071).
"RHB will be following up on this investigation."
CAL OES Report CENTRL No.: 24-0397
THIS MATERIAL EVENT CONTAINS A 'Less than Cat 3' LEVEL OF RADIOACTIVE MATERIAL
Sources that are "Less than IAEA Category 3 sources," are either sources that are very unlikely to cause permanent injury to individuals or contain a very small amount of radioactive material that would not cause any permanent injury. Some of these sources, such as moisture density gauges or thickness gauges that are Category 4, the amount of unshielded radioactive material, if not safely managed or securely protected, could possibly - although it is unlikely - temporarily injure someone who handled it or were otherwise in contact with it, or who were close to it for a period of many weeks. For additional information go to http://www-pub.iaea.org/MTCD/publications/PDF/Pub1227_web.pdf
Power Reactor
Event Number: 56936
Facility: Peach Bottom
Region: 1 State: PA
Unit: [2] [] []
RX Type: [2] GE-4,[3] GE-4
NRC Notified By: Eli Digon
HQ OPS Officer: Natalie Starfish
Region: 1 State: PA
Unit: [2] [] []
RX Type: [2] GE-4,[3] GE-4
NRC Notified By: Eli Digon
HQ OPS Officer: Natalie Starfish
Notification Date: 01/29/2024
Notification Time: 13:32 [ET]
Event Date: 01/29/2024
Event Time: 12:02 [EST]
Last Update Date: 02/01/2024
Notification Time: 13:32 [ET]
Event Date: 01/29/2024
Event Time: 12:02 [EST]
Last Update Date: 02/01/2024
Emergency Class: Non Emergency
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS Actuation - Critical 50.72(b)(3)(iv)(A) - Valid Specif Sys Actuation
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS Actuation - Critical 50.72(b)(3)(iv)(A) - Valid Specif Sys Actuation
Person (Organization):
Dentel, Glenn (R1DO)
Dentel, Glenn (R1DO)
Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
---|---|---|---|---|---|---|
2 | A/R | Y | 100 | Power Operation | 0 | Hot Shutdown |
EN Revision Imported Date: 2/1/2024
EN Revision Text: AUTOMATIC REACTOR SCRAM
The following information was provided by the licensee via email:
"At approximately 1202 EST on 01/29/24, unit 2 experienced a reactor scram caused by a main turbine trip. Investigation is still ongoing."
The following additional information was obtained from the licensee in accordance with Headquarters Operations Officers Report Guidance:
All control rods were fully inserted. The licensee indicated that the turbine trip may have been caused by a power load imbalance, however the cause of the incident is under investigation. The scram was not complex.
Decay heat is currently being removed thru bypass valves dumping to the main condenser. Initially unit 2 lost the use of the bypass valves due to lack of condenser vacuum. Unit 2 used the high pressure coolant injection (HPCI) system in the condenser storage tank (CST) to CST mode to remove decay heat. Residual heat removal was used to keep the torus cool. Condenser vacuum was regained and unit 2 is back to removing decay heat with the turbine bypass valves.
There was no impact to unit 3.
The licensee confirmed there was no impact on the health and safety of the public or plant personnel. The NRC Resident Inspector has been notified.
* * *UPDATE ON 01/29/24 AT 1935 EST FROM PAUL BOKUS TO NATALIE STARFISH* * *
The following information was provided by the licensee via email:
Licensee adds 8-hour non-emergency 10 CFR 50.72(b)(3)(iv)(A) specified system actuation report to original 4-hour non-emergency 10 CFR 50.72(b)(2)(iv)(B) RPS Actuation report.
"At approximately 1202 EST on 01/29/24, unit 2 experienced a reactor scram by a main turbine trip. All control rods inserted. Reactor core isolation cooling system (RCIC) was manually initiated for level control. HPCI was manually initiated for pressure control. Primary containment isolation system (PCIS) Group II and III isolations occurred [specified system actuation]. Investigation is ongoing."
The NRC Resident Inspector has been notified.
EN Revision Text: AUTOMATIC REACTOR SCRAM
The following information was provided by the licensee via email:
"At approximately 1202 EST on 01/29/24, unit 2 experienced a reactor scram caused by a main turbine trip. Investigation is still ongoing."
The following additional information was obtained from the licensee in accordance with Headquarters Operations Officers Report Guidance:
All control rods were fully inserted. The licensee indicated that the turbine trip may have been caused by a power load imbalance, however the cause of the incident is under investigation. The scram was not complex.
Decay heat is currently being removed thru bypass valves dumping to the main condenser. Initially unit 2 lost the use of the bypass valves due to lack of condenser vacuum. Unit 2 used the high pressure coolant injection (HPCI) system in the condenser storage tank (CST) to CST mode to remove decay heat. Residual heat removal was used to keep the torus cool. Condenser vacuum was regained and unit 2 is back to removing decay heat with the turbine bypass valves.
There was no impact to unit 3.
The licensee confirmed there was no impact on the health and safety of the public or plant personnel. The NRC Resident Inspector has been notified.
* * *UPDATE ON 01/29/24 AT 1935 EST FROM PAUL BOKUS TO NATALIE STARFISH* * *
The following information was provided by the licensee via email:
Licensee adds 8-hour non-emergency 10 CFR 50.72(b)(3)(iv)(A) specified system actuation report to original 4-hour non-emergency 10 CFR 50.72(b)(2)(iv)(B) RPS Actuation report.
"At approximately 1202 EST on 01/29/24, unit 2 experienced a reactor scram by a main turbine trip. All control rods inserted. Reactor core isolation cooling system (RCIC) was manually initiated for level control. HPCI was manually initiated for pressure control. Primary containment isolation system (PCIS) Group II and III isolations occurred [specified system actuation]. Investigation is ongoing."
The NRC Resident Inspector has been notified.
Power Reactor
Event Number: 56938
Facility: Grand Gulf
Region: 4 State: MS
Unit: [1] [] []
RX Type: [1] GE-6
NRC Notified By: Joshua Hubbard
HQ OPS Officer: Natalie Starfish
Region: 4 State: MS
Unit: [1] [] []
RX Type: [1] GE-6
NRC Notified By: Joshua Hubbard
HQ OPS Officer: Natalie Starfish
Notification Date: 01/29/2024
Notification Time: 16:56 [ET]
Event Date: 01/29/2024
Event Time: 10:05 [CST]
Last Update Date: 01/29/2024
Notification Time: 16:56 [ET]
Event Date: 01/29/2024
Event Time: 10:05 [CST]
Last Update Date: 01/29/2024
Emergency Class: Non Emergency
10 CFR Section:
50.72(b)(3)(v)(D) - Accident Mitigation
10 CFR Section:
50.72(b)(3)(v)(D) - Accident Mitigation
Person (Organization):
Agrawal, Ami (R4DO)
Agrawal, Ami (R4DO)
Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
---|---|---|---|---|---|---|
1 | N | Y | 100 | Power Operation | 100 | Power Operation |
HIGH PRESSURE CORE SPRAY FAILURE
The following information was provided by the licensee via email:
"At 1005 CST on January 29, 2024, Grand Gulf Nuclear Station was conducting surveillance testing on the high pressure core spray system. During testing, the 1E22F012 minimum flow valve failed to return to the full closed position. The valve went from full open indication to dual indication.
"The event is being reported in accordance with 10 CFR 50.72(b)(3)(v)(D) as an event or condition which could have prevented the fulfillment of a safety function.
"Troubleshooting is in progress.
"The NRC Senior Resident has been notified."
The following additional information was obtained from the licensee in accordance with Headquarters Operations Officers Report Guidance:
All off-site power is available. No other systems are out of service and there are no compensatory measures taken. There is no increase to plant risk.
The following information was provided by the licensee via email:
"At 1005 CST on January 29, 2024, Grand Gulf Nuclear Station was conducting surveillance testing on the high pressure core spray system. During testing, the 1E22F012 minimum flow valve failed to return to the full closed position. The valve went from full open indication to dual indication.
"The event is being reported in accordance with 10 CFR 50.72(b)(3)(v)(D) as an event or condition which could have prevented the fulfillment of a safety function.
"Troubleshooting is in progress.
"The NRC Senior Resident has been notified."
The following additional information was obtained from the licensee in accordance with Headquarters Operations Officers Report Guidance:
All off-site power is available. No other systems are out of service and there are no compensatory measures taken. There is no increase to plant risk.
Power Reactor
Event Number: 55575
Facility: Peach Bottom
Region: 1 State: PA
Unit: [2] [] []
RX Type: [2] GE-4,[3] GE-4
NRC Notified By: Chris Wainaina
HQ OPS Officer: Karen Cotton
Region: 1 State: PA
Unit: [2] [] []
RX Type: [2] GE-4,[3] GE-4
NRC Notified By: Chris Wainaina
HQ OPS Officer: Karen Cotton
Notification Date: 11/14/2021
Notification Time: 08:50 [ET]
Event Date: 11/14/2021
Event Time: 05:25 [EST]
Last Update Date: 01/30/2024
Notification Time: 08:50 [ET]
Event Date: 11/14/2021
Event Time: 05:25 [EST]
Last Update Date: 01/30/2024
Emergency Class: Non Emergency
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS Actuation - Critical
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS Actuation - Critical
Person (Organization):
Henrion, Mark (R1)
Henrion, Mark (R1)
Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
---|---|---|---|---|---|---|
2 | M/R | Y | 100 | Power Operation | 0 | Hot Standby |
EN Revision Imported Date: 1/31/2024
EN Revision Text: MANUAL TRIP DUE TO LOWERING MAIN CONDENSER VACUUM
At 0525 EST, November 14, 2021, "Unit 2 was manually scammed by operations due to lowering main condenser vacuum. This resulted in PCIS (primary containment Isolation system) Group II/III isolation signals. All control rods inserted, and all systems operated as designed."
Unit 3 is unaffected and remains at 100 percent power in Mode 1.
The Resident Inspector was notified.
EN Revision Text: MANUAL TRIP DUE TO LOWERING MAIN CONDENSER VACUUM
At 0525 EST, November 14, 2021, "Unit 2 was manually scammed by operations due to lowering main condenser vacuum. This resulted in PCIS (primary containment Isolation system) Group II/III isolation signals. All control rods inserted, and all systems operated as designed."
Unit 3 is unaffected and remains at 100 percent power in Mode 1.
The Resident Inspector was notified.