Skip to main content

Event Notification Report for September 02, 2023

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
09/01/2023 - 09/02/2023

EVENT NUMBERS
5671056711
Power Reactor
Event Number: 56710
Facility: Nine Mile Point
Region: 1     State: NY
Unit: [2] [] []
RX Type: [1] GE-2,[2] GE-5
NRC Notified By: Kiersten Walker
HQ OPS Officer: Bill Gott
Notification Date: 09/02/2023
Notification Time: 09:46 [ET]
Event Date: 09/02/2023
Event Time: 06:32 [EDT]
Last Update Date: 09/02/2023
Emergency Class: Non Emergency
10 CFR Section:
50.72(b)(2)(iv)(A) - Eccs Injection 50.72(b)(2)(iv)(B) - RPS Actuation - Critical 50.72(b)(3)(iv)(A) - Valid Specif Sys Actuation
Person (Organization):
Dentel, Glenn (R1DO)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 A/R Y 100 Power Operation 0 Hot Shutdown
Event Text
AUTOMATIC REACTOR SCRAM DUE TO FEEDWATER TRANSIENT

The following information was provided by the licensee via email:

"On 9/2/2023 at 0632 EDT, a feedwater transient occurred resulting in an reactor protection system (RPS) automatic reactor scram on low level (Level 3, 159.3 inches). Following the scram, reactor water level dropped below Level 2 (108.8 inches) resulting in a Group 2 recirculation sample system isolation, Group 3 traveling in-core probe (TIP) isolation valve isolation, Group 6 and 7 reactor water cleanup isolation, and Group 9 containment purge isolations. All control rods inserted as expected. High pressure core spray and reactor core isolation cooling initiated and injected as expected. ECCS systems have been secured and normal reactor pressure and level control has been established for hot shutdown. Nine Mile Point Unit 2 is stable and in Mode 3.

"These 4 hour and 8 hour non-emergency reports are being made in accordance with 10 CFR 50.72(b)(2) (iv)(A), 10 CFR 50.72(b)(2)(iv)(B), and 10 CFR 50.72(b)(3)(iv)(A).

"The NRC Resident was informed. There was no impact on Unit 1."


Fuel Cycle Facility
Event Number: 56711
Facility: Honeywell International, Inc.
Region: 2     State: IL
Unit: [] [] []
RX Type: Uranium Hexafluoride Production
Comments: Uf6 Conversion (Dry Process)


NRC Notified By: Jon Bernard
HQ OPS Officer: Bill Gott
Notification Date: 09/02/2023
Notification Time: 10:06 [ET]
Event Date: 09/02/2023
Event Time: 08:17 [CDT]
Last Update Date: 09/02/2023
Emergency Class: Alert
10 CFR Section:
50.72(a) (1) (i) - Emergency Declared
Person (Organization):
Miller, Mark (R2DO)
NMSS_EVENTS_NOTIFICATION (EMAIL)
Dudes, Laura (Region 2)
Lubinski, John (NMSS)
Grant, Jeffery (IR)
Event Text
ALERT DECLARED DUE TO UF6 RELEASE

The following information was provided by the licensee via email:

"On 09/02/2023, Honeywell declared a 'Plant Emergency' at 0815 CDT and upgraded to an 'Alert' at 0835 CDT in accordance with the Honeywell Emergency Response Plan due to a uranium hexafluoride leak on the kinney pump system."

Notified DHS Senior Watch Officer, FEMA Operations Center, CISA Central watch officer, DOE Operations Center, HHS Operations Center, EPA Emergency Operations Center, USDA Operations Center, FDA EOC (email), FEMA NWC (email), and DHS Nuclear SSA (email), FEMA NRCC (email) and CWMD watch desk (email).

* * * UPDATE ON 9/2/2023 AT 2241 EDT FROM HONEYWELL INTERNATIONAL TO IAN B. HOWARD * * *

"The 'All Clear' was declared at 2115 CDT on 09/02/2023. There were no injuries related to this incident. This statement constitutes the NRC notification related to the incident. Honeywell is currently investigating the cause of the event."

Notified R2DO (Miller), NMSS/DFM Division Director (Helton), NMSS Events Notification (email), IRMOC (Grant), DHS SWO, FEMA Ops Center, USDA Ops Center, HHS Ops Center, DOE Ops Center, CISA Central Watch Officer, EPA EOC, FDA EOC (email), FEMA NWC (email), DHS Nuclear SSA (email), DHS NRCC (email), FEMA NRCC SASC (email), FERC (email).