Skip to main content

Event Notification Report for March 17, 2017

U.S. Nuclear Regulatory Commission
Operations Center

Event Reports For
03/16/2017 - 03/17/2017

** EVENT NUMBERS **


52615

Power Reactor Event Number: 52615
Facility: COLUMBIA GENERATING STATION
Region: 4 State: WA
Unit: [2] [ ] [ ]
RX Type: [2] GE-5
NRC Notified By: DON GREGOIRE
HQ OPS Officer: BETHANY CECERE
Notification Date: 03/16/2017
Notification Time: 15:07 [ET]
Event Date: 03/14/2017
Event Time: 16:00 [PDT]
Last Update Date: 03/16/2017
Emergency Class: NON EMERGENCY
10 CFR Section:
21.21(d)(3)(i) - DEFECTS AND NONCOMPLIANCE
Person (Organization):
NEIL OKEEFE (R4DO)
HAROLD GRAY (R1DO)
FRANK EHRHARDT (R2DO)
KARLA STOEDTER (R3DO)
PART 21/50.55 REACTO (EMAI)

Unit SCRAM Code RX CRIT Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 98 Power Operation 98 Power Operation

Event Text

PART 21 NOTIFICATION - EVALUATION OF A DEVIATION - STARTER CONTACTOR FAILURE

"Pursuant to 10 CFR Part 21, this is a non-emergency notification by Energy Northwest concerning a defect in Size 1 Freedom Series Starters with nominal 120 VAC coils manufactured by AZZ/NLI [Nuclear Logistics Inc.] used at Columbia Generating Station.

"On February 8, 2017 Energy Northwest was notified by NLI of a deviation associated with starter contactors used at Columbia that failed to close due to overheating of the starter coil. The coils that were provided were determined to not meet specified voltage ratings.

"The evaluation completed by Energy Northwest on March 14, 2017 concluded that the deviation did create a Substantial Safety Hazard, and is reportable under 10 CFR 21.21(d)(1) as a defect.

"A 30 day report will be issued by April 13, 2017 per 10 CFR 21.21(d)(4)."

The licensee performed a prompt operability assessment for the two starters currently installed.

The licensee will notify the NRC Resident Inspector.

Page Last Reviewed/Updated Wednesday, March 24, 2021

Page Last Reviewed/Updated Wednesday, March 24, 2021