Skip to main content

Alert

The NRC is shutdown due to the lapse in appropriations. Exempted activities to maintain critical health and safety activities and progress on critical activities, including activities outlined in Executive Order 14300, as described in the OMB Approved NRC Lapse Plan will continue.

Event Notification Report for July 11, 2011

U.S. Nuclear Regulatory Commission
Operations Center

Event Reports For
07/08/2011 - 07/11/2011

** EVENT NUMBERS **


47029 47035 47036 47037 47039 47040 47041

To top of page
Agreement State Event Number: 47029
Rep Org: TEXAS DEPARTMENT OF HEALTH
Licensee: TEXAS QA SERVICE, INC
Region: 4
City: GRAND PRAIRIE State: TX
County:
License #: 04601
Agreement: Y
Docket:
NRC Notified By: KAREN BLANCHARD
HQ OPS Officer: JOHN KNOKE
Notification Date: 07/06/2011
Notification Time: 17:18 [ET]
Event Date: 06/27/2011
Event Time: [CDT]
Last Update Date: 07/06/2011
Emergency Class: NON EMERGENCY
10 CFR Section:
AGREEMENT STATE
Person (Organization):
BOB HAGAR (R4DO)
RICHARD TURTIL (FSME)

Event Text

AGREEMENT STATE REPORT - IRIDIUM SOURCE DISCONNECTED FROM RADIOGRAPHY CAMERA

The following information was received from the State of Texas via e-mail:

"On July 6, 2011, the Agency [Texas Department of Health] received a written report from the licensee's Radiation Safety Officer (RSO) that on June 27, 2011, there was a source disconnection at a temporary field site [Dralco, Inc] in Weatherford, Texas. Upon discovering the disconnection, the radiographers roped off the area at the 2 millirem/hour boundary and notified the RSO.

"The RSO arrived on site and confirmed that the source was disconnected. The RSO performed the retrieval by removing the source tube from the camera, shaking the source out of the source tube and placing a lead shield and shot bag(s) over the source with the pigtail exposed. He reconnected the drive cable and the source was cranked back into the camera. The camera was disconnected so that the drive cable and the pigtail connectors could be inspected. No damage was noted and the camera was immediately returned to service.

"The RSO stayed on site approximately one hour to make sure there were no more issues. The RSO stated that the radiographers had failed to connect the pigtail to the drive cable before cranking out the source. The RSO received a dose of 52 mrem. Corrective action includes the event being discussed at the next safety meeting, the radiographers (who were trainers) were instructed to pay attention to safety and the process of connecting the drive cable to the source."

Camera: Amersham Model 660B, SN: 4894
Source: QSA Global Model A424-9, SN: 69176B, Iridium-192, 22 curies

Texas Incident #: I-8867

To top of page
Power Reactor Event Number: 47035
Facility: FORT CALHOUN
Region: 4 State: NE
Unit: [1] [ ] [ ]
RX Type: (1) CE
NRC Notified By: ERICK MATZKE
HQ OPS Officer: JOHN KNOKE
Notification Date: 07/08/2011
Notification Time: 13:48 [ET]
Event Date: 05/10/2011
Event Time: 04:30 [CDT]
Last Update Date: 07/08/2011
Emergency Class: NON EMERGENCY
10 CFR Section:
50.73(a)(1) - INVALID SPECIF SYSTEM ACTUATION
Person (Organization):
BOB HAGAR (R4DO)

Unit SCRAM Code RX CRIT Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N N 0 Cold Shutdown 0 Cold Shutdown

Event Text

60 DAY REPORT - EMERGENCY DIESEL GENERATOR STARTED DUE TO INVALID SIGNAL

"This 10CFR50.73(a)(1) report is a 60-day telephone notification in lieu of a written licensee event report being made under 10CFR50.73(a)(2)(iv)(A). On May 10, 2011 at 0430 CDT, during installation of the new loss of offsite power relay, Emergency Diesel Generator 2, started (a complete start) due to an invalid signal but remained operable while running as a backup power supply to its bus. The unit was in a refueling outage at the time. Offsite power was not lost and the diesel bus remained energized from offsite power and was operable. The diesel was subsequently secured."

The licensee has notified the NRC Resident Inspector.

To top of page
Part 21 Event Number: 47036
Rep Org: EMERSON PROCESS MANAGEMENT
Licensee: EMERSON PROCESS MANAGEMENT
Region: 3
City: MARSHALLTOWN State: IA
County:
License #:
Agreement: Y
Docket:
NRC Notified By: TRISH CROSSER
HQ OPS Officer: VINCE KLCO
Notification Date: 07/08/2011
Notification Time: 14:24 [ET]
Event Date: 05/13/2011
Event Time: [CDT]
Last Update Date: 07/08/2011
Emergency Class: NON EMERGENCY
10 CFR Section:
21.21 - UNSPECIFIED PARAGRAPH
Person (Organization):
DAVID HILLS (R3DO)
BOB HAGAR (R4DO)
PART 21 GRP ()

Event Text

VALVE FAILED LEAK TEST DUE TO A DISC/SHAFT ASSEMBLY MACHINING ISSUE

The following information was received by facsimile:

"After a valve failed a leak test, it was determined that a fixture to machine the valve disc was missing one of the locating pins that maintained the integrity of the shaft bore centerline when machining. It was determined that the pin was missing from the fixture from January 8, 2011, to April 7, 2011 .

"Fisher has conducted a review and determined that the only ASME Section III code and commercial grade dedicated parts machined during this time that would use this fixture were the parts used for the orders referenced [below].

"Fisher Controls has implemented a corrective action program to address this issue.

"Although this notice is dated July 5, 2011 , Palo Verde was officially notified May 13, 2011, when Fisher first became aware of this issue. In the mean time, all affected discs have been returned to Fisher Controls for evaluation.

"Subject: NPS 16 Type A11 Disc/Shaft Assemblies for Palo Verde Orders 500541604 and 500548617 (Fisher Orders 019-F514977 and 019-F515346)."

To top of page
Non-Agreement State Event Number: 47037
Rep Org: WILCOX ASSOCIATES
Licensee: WILCOX ASSOCIATES
Region: 3
City: CADILLAC State: MI
County:
License #: 21-23314
Agreement: N
Docket:
NRC Notified By: JOSH GOTTSCHALL
HQ OPS Officer: VINCE KLCO
Notification Date: 07/08/2011
Notification Time: 13:34 [ET]
Event Date: 07/08/2011
Event Time: 11:30 [EDT]
Last Update Date: 07/08/2011
Emergency Class: NON EMERGENCY
10 CFR Section:
30.50(b)(2) - SAFETY EQUIPMENT FAILURE
Person (Organization):
DAVID HILLS (R3DO)
RICHARD TURTIL (FSME)

Event Text

DAMAGED MOISTURE DENSITY GAUGE

A gauge handle on a portable Troxler Gauge Model 3440 (S/N #16851) was run over by a truck in the Hastings, Michigan area. The measurement and source handle rod was bent. The licensee performed an area survey and no leakage was detected. The density gauge source was not exposed. The licensee plans to ship the damaged gauge to the Troxler Company for repair or replacement.

To top of page
Power Reactor Event Number: 47039
Facility: SUMMER
Region: 2 State: SC
Unit: [1] [ ] [ ]
RX Type: [1] W-3-LP
NRC Notified By: ERIC RUMFELT
HQ OPS Officer: VINCE KLCO
Notification Date: 07/08/2011
Notification Time: 16:00 [ET]
Event Date: 07/07/2011
Event Time: 11:00 [EDT]
Last Update Date: 07/08/2011
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(xi) - OFFSITE NOTIFICATION
Person (Organization):
BRIAN BONSER (R2DO)

Unit SCRAM Code RX CRIT Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation

Event Text

OFFSITE NOTIFICATION DUE TO A CONTAINED ON-SITE LIQUID RADWASTE LEAK

"This notification is being made under 10 CFR 50.72(b)(2)(xi) of a situation related to the protection of the environment for which a notification to a state agency has been made. On July 8, 2011, South Carolina Electric & Gas Company (SCE&G) made a voluntary notification to the South Carolina Department of Health and Environmental Control (SCDHEC) in accordance with the Nuclear Energy Institute (NEI) Groundwater Protection Initiative for an on-site leak that may exceed 100 gallons. The leak was entirely contained within the V. C. Summer Nuclear Station site boundary.

"On July 7, 2011 during a routine inspection, a leak was discovered in a liquid radwaste line upstream from its final discharge point and downstream of the release radiation monitors. This line contains processed liquid radwaste that has been sampled and permitted for release. The leak occurred inside a containment enclosure which overflowed. The enclosure was drained and the liquid was returned to the plant for disposal. The leak has been isolated and all radwaste release via this pathway has been suspended. The last inspection of this equipment was conducted on February 14, 2011, and revealed no external leakage."

The licensee notified the NRC Resident Inspector.

To top of page
Power Reactor Event Number: 47040
Facility: COOK
Region: 3 State: MI
Unit: [1] [2] [ ]
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: BEN HUFFMAN
HQ OPS Officer: STEVE SANDIN
Notification Date: 07/11/2011
Notification Time: 03:00 [ET]
Event Date: 07/11/2011
Event Time: 04:00 [EDT]
Last Update Date: 07/11/2011
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(xiii) - LOSS COMM/ASMT/RESPONSE
Person (Organization):
DAVID HILLS (R3DO)

Unit SCRAM Code RX CRIT Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
2 N Y 100 Power Operation 100 Power Operation

Event Text

UNAVAILABILITY OF TSC VENTILATION SYSTEM DUE TO SCHEDULED MAINTENANCE

"At 0400 EDT on Monday, July 11, 2011, the Cook Nuclear Plant (CNP) Technical Support Center (TSC) air conditioning and charcoal filtration systems will be removed from service for scheduled maintenance.

"Under certain accident conditions the TSC may become unavailable due to the inability of the air conditioning and charcoal filtration systems to maintain a habitable atmosphere. Compensatory measures exist to relocate TSC personnel to the unaffected unit's control room if necessary.

"TSC ventilation system maintenance is scheduled to be completed by 2000 EDT on Monday, July 11, 2011.

"The licensee has notified the NRC Resident Inspector.

"This notification is being made in accordance with 10 CFR 50.72 (b)(3)(xiii) due to the loss of an emergency response facility."

To top of page
Power Reactor Event Number: 47041
Facility: PRAIRIE ISLAND
Region: 3 State: MN
Unit: [1] [2] [ ]
RX Type: [1] W-2-LP,[2] W-2-LP
NRC Notified By: STEPHEN SEILHYMER
HQ OPS Officer: MARK ABRAMOVITZ
Notification Date: 07/11/2011
Notification Time: 04:00 [ET]
Event Date: 07/11/2011
Event Time: 01:25 [CDT]
Last Update Date: 07/11/2011
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(xi) - OFFSITE NOTIFICATION
Person (Organization):
DAVID HILLS (R3DO)

Unit SCRAM Code RX CRIT Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
2 N Y 100 Power Operation 100 Power Operation

Event Text

INADVERTENT EMERGENCY SIREN ACTIVATION COINCIDENT WITH ADVERSE WEATHER

"At approximately 0125 CDT on July 11, 2011 licensee was notified by Goodhue County Sheriff's Department of an inadvertent emergency siren activation (R17) in the city of Red Wing, MN. The Sheriff's Department deactivated the siren and notified the siren vendor. Siren initiation was coincident with severe storm activity in the area, including lighting strikes. Siren remains out of service and is the only siren out of service within the 10 mile Emergency Planning Zone (EPZ)."

The licensee informed the NRC Resident Inspector.

Page Last Reviewed/Updated Thursday, March 25, 2021

Page Last Reviewed/Updated Thursday, March 25, 2021