Skip to main content

Alert

The NRC is shutdown due to the lapse in appropriations. Exempted activities to maintain critical health and safety activities and progress on critical activities, including activities outlined in Executive Order 14300, as described in the OMB Approved NRC Lapse Plan will continue.

Event Notification Report for March 31, 2003






                    U.S. Nuclear Regulatory Commission

                              Operations Center



                              Event Reports For

                           03/28/2003 - 03/31/2003



                              ** EVENT NUMBERS **



39709  39711  39712  39713  39714  





+------------------------------------------------------------------------------+

|Power Reactor                                    |Event Number:   39709       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| FACILITY: CALVERT CLIFFS           REGION:  1  |NOTIFICATION DATE: 03/28/2003|

|    UNIT:  [1] [2] []                STATE:  MD |NOTIFICATION TIME: 02:28[EST]|

|   RXTYPE: [1] CE,[2] CE                        |EVENT DATE:        03/28/2003|

+------------------------------------------------+EVENT TIME:        00:45[EST]|

| NRC NOTIFIED BY:  JIM GROOM                    |LAST UPDATE DATE:  03/28/2003|

|  HQ OPS OFFICER:  STEVE SANDIN                 +-----------------------------+

+------------------------------------------------+PERSON          ORGANIZATION |

|EMERGENCY CLASS:          NON EMERGENCY         |JOHN WHITE           R1      |

|10 CFR SECTION:                                 |                             |

|APRE 50.72(b)(2)(xi)     OFFSITE NOTIFICATION   |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|1     N          Y       100      Power Operation  |100      Power Operation  |

|2     N          N       0        Refueling        |0        Refueling        |

|                                                   |                          |

+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| POTENTIAL MEDIA INTEREST DUE TO STATE POLICE SEARCH OF THE OWNER CONTROLLED  |

| AREA                                                                         |

|                                                                              |

| The Calvert Control Center in Prince Frederick County received an anonymous  |

| call through the 911 operator which prompted the Maryland State Police to    |

| furnish additional officers to the site for a search of the woodline area of |

| the owner controlled property.  The licensee will inform their media group   |

| due to the potential media interest and has informed both state/local        |

| agencies and the NRC resident inspector.                                     |

+------------------------------------------------------------------------------+



+------------------------------------------------------------------------------+

|General Information or Other                     |Event Number:   39711       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| REP ORG:  FOX CHASE CANCER CENTER              |NOTIFICATION DATE: 03/28/2003|

|LICENSEE:  FOX CHASE CANCER CENTER              |NOTIFICATION TIME: 14:30[EST]|

|    CITY:  PHILADELPHIA             REGION:  1  |EVENT DATE:        04/16/2000|

|  COUNTY:                            STATE:  PA |EVENT TIME:             [EST]|

|LICENSE#:  37-02766-01           AGREEMENT:  N  |LAST UPDATE DATE:  03/28/2003|

|  DOCKET:                                       |+----------------------------+

|                                                |PERSON          ORGANIZATION |

|                                                |PAMELA HENDERSON     R1      |

|                                                |SUSAN FRANT          NMSS    |

+------------------------------------------------+                             |

| NRC NOTIFIED BY:  KAREN SHEEHAN                |                             |

|  HQ OPS OFFICER:  GERRY WAIG                   |                             |

+------------------------------------------------+                             |

|EMERGENCY CLASS:          NON EMERGENCY         |                             |

|10 CFR SECTION:                                 |                             |

|BLO1 20.2201(a)(1)(i)    LOST/STOLEN LNM>1000X  |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

+------------------------------------------------------------------------------+



                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| NRC LICENSEE TRANSFERRED RADIOACTIVE MATERIAL TO UNLICENSED ENTITY           |

|                                                                              |

| On April 16, 2000, the licensee transferred a Varian 6/100 linear            |

| accelerator, with a 41 millicurie depleted uranium source, to Centura X-Ray, |

| Cleveland, Ohio, an unlicensed entity. The transfer was part of an equipment |

| upgrade made between the licensee and Siemens Medical Systems Inc.           |

|                                                                              |

| Siemens sold the Varian 6/100 to Linac Systems, Lakewood, New Jersey who in  |

| turn sold the equipment to eRad Therapy, Inc. of Bothell, Washington.  eRad  |

| Therapy transported the device to the therapy division of Centura X-ray.     |

|                                                                              |

| The depleted uranium is currently in the possession of a licensed low level  |

| waste storage facility awaiting burial at an appropriate waste disposal      |

| facility.                                                                    |

+------------------------------------------------------------------------------+



+------------------------------------------------------------------------------+

|Power Reactor                                    |Event Number:   39712       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| FACILITY: HATCH                    REGION:  2  |NOTIFICATION DATE: 03/29/2003|

|    UNIT:  [] [2] []                 STATE:  GA |NOTIFICATION TIME: 04:44[EST]|

|   RXTYPE: [1] GE-4,[2] GE-4                    |EVENT DATE:        03/29/2003|

+------------------------------------------------+EVENT TIME:        02:55[EST]|

| NRC NOTIFIED BY:  EDWEN URQUHART               |LAST UPDATE DATE:  03/29/2003|

|  HQ OPS OFFICER:  MIKE RIPLEY                  +-----------------------------+

+------------------------------------------------+PERSON          ORGANIZATION |

|EMERGENCY CLASS:          NON EMERGENCY         |RUDOLPH BERNHARD     R2      |

|10 CFR SECTION:                                 |                             |

|AINA 50.72(b)(3)(v)(A)   POT UNABLE TO SAFE SD  |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|                                                   |                          |

|2     N          Y       1        Startup          |1        Startup          |

|                                                   |                          |

+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| HPCI TURBINE FAILS TO COME TO SPEED DURING SURVEILLANCE TEST                 |

|                                                                              |

| "While starting up Unit Two reactor from a planned refueling/maintenance     |

| outage, the HPCI system would not pass the required tech spec surveillance   |

| when tested at 160 psig reactor pressure.  The HPCI turbine failed to come   |

| up to speed due to its turbine steam control valve did not open after the    |

| turbine stop valve was opened per system operability surveillance.  The      |

| system engineer and maintenance are investigating the speed control circuit  |

| at this time."                                                               |

|                                                                              |

| The licensee has notified the NRC Resident Inspector.                        |

+------------------------------------------------------------------------------+



+------------------------------------------------------------------------------+

|Power Reactor                                    |Event Number:   39713       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| FACILITY: SALEM                    REGION:  1  |NOTIFICATION DATE: 03/29/2003|

|    UNIT:  [] [2] []                 STATE:  NJ |NOTIFICATION TIME: 07:15[EST]|

|   RXTYPE: [1] W-4-LP,[2] W-4-LP                |EVENT DATE:        03/29/2003|

+------------------------------------------------+EVENT TIME:        04:42[EST]|

| NRC NOTIFIED BY:  JOHN GARECHT                 |LAST UPDATE DATE:  03/29/2003|

|  HQ OPS OFFICER:  MIKE RIPLEY                  +-----------------------------+

+------------------------------------------------+PERSON          ORGANIZATION |

|EMERGENCY CLASS:          NON EMERGENCY         |PAMELA HENDERSON     R1      |

|10 CFR SECTION:                                 |                             |

|ARPS 50.72(b)(2)(iv)(B)  RPS ACTUATION - CRITICA|                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|                                                   |                          |

|2     M/R        Y       80       Power Operation  |0        Hot Standby      |

|                                                   |                          |

+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| MANUAL REACTOR TRIP DUE TO LOSS OF SECONDARY CIRCULATING WATER PUMPS         |

|                                                                              |

| "Salem Unit 2 was manually tripped in response to loss of circulating water  |

| pumps.  Loss of circulators was caused by heavy grass intrusion from the     |

| Delaware River.  At time of trip, a load reduction was in progress and power |

| level was approximately 80%.  All safety systems operated as designed during |

| and after the reactor trip.  Unit 2 is currently stable in Mode 3 at normal  |

| operating temperature and pressure.  All reactor cooling pumps are in        |

| service and core cooling is being supported by auxiliary feedwater pumps and |

| main steam dumps to the condenser.  No safety systems or equipment was out   |

| of service at the time of the trip.  Salem Unit 1 was also affected by the   |

| heavy river grass conditions and is currently in Mode 1 and stable at 55%    |

| reactor power."                                                              |

|                                                                              |

| The licensee has notified the NRC Resident Inspector.                        |

+------------------------------------------------------------------------------+



+------------------------------------------------------------------------------+

|Power Reactor                                    |Event Number:   39714       |

+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+

| FACILITY: PALO VERDE               REGION:  4  |NOTIFICATION DATE: 03/29/2003|

|    UNIT:  [] [] [3]                 STATE:  AZ |NOTIFICATION TIME: 13:41[EST]|

|   RXTYPE: [1] CE,[2] CE,[3] CE                 |EVENT DATE:        03/29/2003|

+------------------------------------------------+EVENT TIME:        04:00[MST]|

| NRC NOTIFIED BY:  DAN MARKS                    |LAST UPDATE DATE:  03/29/2003|

|  HQ OPS OFFICER:  HOWIE CROUCH                 +-----------------------------+

+------------------------------------------------+PERSON          ORGANIZATION |

|EMERGENCY CLASS:          NON EMERGENCY         |BLAIR SPITZBERG      R4      |

|10 CFR SECTION:                                 |                             |

|ADEG 50.72(b)(3)(ii)(A)  DEGRADED CONDITION     |                             |

|                                                |                             |

|                                                |                             |

|                                                |                             |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |

+-----+----------+-------+--------+-----------------+--------+-----------------+

|                                                   |                          |

|                                                   |                          |

|3     N          N       0        Hot Shutdown     |0        Hot Shutdown     |

+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   

+------------------------------------------------------------------------------+

| DEGRADED CONDITION DUE TO LEAKAGE AT SMALL BORE INCONEL 600 PENETRATIONS     |

|                                                                              |

| The following information was received from the licensee via facsimile:      |

|                                                                              |

| "The following event description is based on information currently           |

| available. If through subsequent reviews of this event, additional           |

| information is identified that is pertinent to this event or alters the      |

| information being provided at this time, a follow-up notification will be    |

| made via the ENS or under the reporting requirements of 10CFR50.73.          |

|                                                                              |

| "On March 29, 2003, at approximately 04:00 Mountain Standard Time (MST)      |

| engineering personnel performing preplanned visual examinations of reactor   |

| coolant System (RCS) piping in accordance with procedure requirements        |

| discovered boric acid residue on three RCS small bore Inconel 600            |

| penetrations. One location was the RCS hot leg in-service thermowell         |

| 3JRCBTW0112HB.  The visual observation was characterized as a small white    |

| trail of boron residue running down the hot leg approximately 2 inches.      |

| There were no signs of dripping, spraying, puddles of liquid, or liquid      |

| running down the nozzle or hot leg. The residue appeared dry. The other two  |

| were on pressurizer heater sleeves (nozzles) A-4 and A-18. The visual        |

| observation at these two locations was characterized as a small white        |

| buildup of boron residue around the heater sleeve as the sleeve enters the   |

| pressurizer bottom head. There does not appear to be residue running down    |

| the outside of the sleeves. There were no signs of dripping, spraying,       |

| puddles of liquid, or liquid running down the nozzle or [pressurizer]. The   |

| residue appeared dry.                                                        |

|                                                                              |

| "Technical Specifications (TS) Limiting Condition for Operation (LCO) 3.4.14 |

| permits no reactor coolant system (RCS) pressure boundary leakage and        |

| therefore, the discovery of leakage (presumed boric acid residue) from the   |

| hot leg thermowell and the pressurizer heater sleeves was a degradation of a |

| principal safety barrier. Therefore, the ENS notification of this event is   |

| in accordance with 10CFR50.72(b)(3)(ii). The control room personnel entered  |

| LCO 3.4.14 Condition B and are continuing to place the plant in Mode 5. The  |

| RCS was being cooled down in preparation for Unit 3's tenth refueling        |

| outage. At the time of discovery, the RCS was at approximately 520 degrees F |

| and 2218 psia.                                                               |

|                                                                              |

| "An investigation of this event will be conducted in accordance with the     |

| PVNGS [Palo Verde Nuclear Generating Station] corrective action program. The |

| cracking of Alloy 600 components both at Palo Verde and industry-wide has    |

| been attributed to axially oriented, primary water stress corrosion cracking |

| (PWSCC). PWSCC is not considered a significant threat to the structural      |

| integrity of the RCS boundary, thermowell, or heater sleeves as this type of |

| cracking typically results only in small leaks.                              |

|                                                                              |

| "The bases for this conclusion is that if PWSCC occurred at Palo Verde, the  |

| cracks would be predominately axial in orientation. As in this case, the     |

| cracks would result in visibly detectable leakage that would be apparent     |

| during visual examinations, performed as part of walkdown inspections,       |

| before significant damage to the reactor coolant boundary occurred.          |

|                                                                              |

| "Palo Verde has a program for replacing the Alloy 600 hot leg thermowells.   |

| This thermowell was scheduled for replacement during this refueling outage.  |

| The plans to replace the thermowell remain unchanged.                        |

|                                                                              |

| "A mechanical nozzle sleeve assembly (MNSA) will be installed on each of the |

| pressurizer heater sleeves.                                                  |

|                                                                              |

| "No ESF actuations occurred and none were required. There were no            |

| structures, systems, or components that were inoperable at the time of       |

| discovery that contributed to this condition. There were no failures that    |

| rendered a train of a safety system inoperable and no failures of components |

| with multiple functions were involved.  The event did not result in the      |

| release of radioactivity to the environment and did not adversely affect the |

| safe operation of the plant or health and safety of the public."             |

|                                                                              |

| The licensee has informed the NRC Resident Inspector.                        |

+------------------------------------------------------------------------------+                 

Page Last Reviewed/Updated Thursday, March 25, 2021

Page Last Reviewed/Updated Thursday, March 25, 2021