Event Notification Report for November 22, 2000
U.S. Nuclear Regulatory Commission Operations Center Event Reports For 11/21/2000 - 11/22/2000 ** EVENT NUMBERS ** 37539 37540 37541 37542 37543 37544 +------------------------------------------------------------------------------+ |Power Reactor |Event Number: 37539 | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ | FACILITY: FITZPATRICK REGION: 1 |NOTIFICATION DATE: 11/21/2000| | UNIT: [1] [] [] STATE: NY |NOTIFICATION TIME: 01:12[EST]| | RXTYPE: [1] GE-4 |EVENT DATE: 11/20/2000| +------------------------------------------------+EVENT TIME: 23:10[EST]| | NRC NOTIFIED BY: MIKE RASTLEY |LAST UPDATE DATE: 11/21/2000| | HQ OPS OFFICER: DOUG WEAVER +-----------------------------+ +------------------------------------------------+PERSON ORGANIZATION | |EMERGENCY CLASS: N/A |CURTIS COWGILL R1 | |10 CFR SECTION: | | |AINB 50.72(b)(2)(iii)(B) POT RHR INOP | | |AIND 50.72(b)(2)(iii)(D) ACCIDENT MITIGATION | | |NLCO TECH SPEC LCO A/S | | | | | +-----+----------+-------+--------+-----------------+--------+-----------------+ |UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE | +-----+----------+-------+--------+-----------------+--------+-----------------+ |1 N Y 75 Power Operation |72 Power Operation | | | | | | | +------------------------------------------------------------------------------+ EVENT TEXT +------------------------------------------------------------------------------+ | HPCI INOPERABLE - TURBINE EXHAUST LINE FLOODED | | | | HPCI turbine exhaust drain pot level switch has malfunctioned. This has | | potentially led to a condition where exhaust line from the turbine is | | flooded. GE SIL 580 recognizes that a slug of water can create a momentary | | high pressure and rupture both exhaust line rupture diaphragms if HPCI | | should initiate. | | | | HPCI system has been declared inoperable and the licensee entered a 7 day | | LCO. | | | | The NRC resident inspector has been notified. | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ |Power Reactor |Event Number: 37540 | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ | FACILITY: FITZPATRICK REGION: 1 |NOTIFICATION DATE: 11/21/2000| | UNIT: [1] [] [] STATE: NY |NOTIFICATION TIME: 11:03[EST]| | RXTYPE: [1] GE-4 |EVENT DATE: 11/21/2000| +------------------------------------------------+EVENT TIME: 10:22[EST]| | NRC NOTIFIED BY: AMBRAMSKY |LAST UPDATE DATE: 11/21/2000| | HQ OPS OFFICER: DOUG WEAVER +-----------------------------+ +------------------------------------------------+PERSON ORGANIZATION | |EMERGENCY CLASS: N/A |CURTIS COWGILL R1 | |10 CFR SECTION: | | |AARC 50.72(b)(1)(v) OTHER ASMT/COMM INOP | | | | | | | | | | | +-----+----------+-------+--------+-----------------+--------+-----------------+ |UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE | +-----+----------+-------+--------+-----------------+--------+-----------------+ |1 N Y 93 Power Operation |93 Power Operation | | | | | | | +------------------------------------------------------------------------------+ EVENT TEXT +------------------------------------------------------------------------------+ | LOSS OF POWER TO THE EMERGENCY OPERATIONS FACILITY (EOF) | | | | The loss of power to the EOF impairs the ability of the licensee to carry | | out the plant's emergency plan. A snow storm is being blamed for the loss | | of power. | | | | The licensee notified the NRC resident inspector. | | | | (Refer to event number 37541 for a related event at Nine Mile Point.) | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ |Power Reactor |Event Number: 37541 | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ | FACILITY: NINE MILE POINT REGION: 1 |NOTIFICATION DATE: 11/21/2000| | UNIT: [1] [2] [] STATE: NY |NOTIFICATION TIME: 11:29[EST]| | RXTYPE: [1] GE-2,[2] GE-5 |EVENT DATE: 11/21/2000| +------------------------------------------------+EVENT TIME: 09:50[EST]| | NRC NOTIFIED BY: QUINTON HICKS |LAST UPDATE DATE: 11/21/2000| | HQ OPS OFFICER: DOUG WEAVER +-----------------------------+ +------------------------------------------------+PERSON ORGANIZATION | |EMERGENCY CLASS: N/A |CURTIS COWGILL R1 | |10 CFR SECTION: | | |AARC 50.72(b)(1)(v) OTHER ASMT/COMM INOP | | | | | | | | | | | +-----+----------+-------+--------+-----------------+--------+-----------------+ |UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE | +-----+----------+-------+--------+-----------------+--------+-----------------+ |1 N Y 100 Power Operation |100 Power Operation | |2 N Y 100 Power Operation |100 Power Operation | | | | +------------------------------------------------------------------------------+ EVENT TEXT +------------------------------------------------------------------------------+ | LOSS OF POWER TO THE EMERGENCY OPERATIONS FACILITY (EOF) | | | | The licensee reported that power was lost to the EOF at 0950 and was | | restored at 1045. This facility serves both the NMP units as well as | | Fitzpatrick. The licensee notified the NRC resident inspector. | | | | (Refer to event number 37540 for a related event at Fitzpatrick.) | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ |Other Nuclear Material |Event Number: 37542 | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ | REP ORG: BEST INDUSTRIES |NOTIFICATION DATE: 11/21/2000| |LICENSEE: BEST INDUSTRIES |NOTIFICATION TIME: 12:02[EST]| | CITY: SPRINGFIELD REGION: 2 |EVENT DATE: 11/21/2000| | COUNTY: STATE: VA |EVENT TIME: 10:00[EST]| |LICENSE#: 45-19757-01 AGREEMENT: N |LAST UPDATE DATE: 11/21/2000| | DOCKET: |+----------------------------+ | |PERSON ORGANIZATION | | |MIKE ERNSTES R2 | | |JOHN HICKEY NMSS | +------------------------------------------------+ | | NRC NOTIFIED BY: JOE WANG | | | HQ OPS OFFICER: BOB STRANSKY | | +------------------------------------------------+ | |EMERGENCY CLASS: N/A | | |10 CFR SECTION: | | |BAAA 20.1906(d) SURFACE CONT/ EXT RAD | | | | | | | | | | | | | | +------------------------------------------------------------------------------+ EVENT TEXT +------------------------------------------------------------------------------+ | 10 CFR PART 20.1906(d) REPORT | | | | One of three Type A shipping packages received from Baylor University | | exceeded the limit for surface radiation readings (200 mR/hr). The licensee | | reported that the package was reading 2.7 R/hr at the surface of the | | package, and 65 mR/hr at 1 meter. The package has been placed in safe | | storage. The licensee will contact Baylor University and the shipper | | (FedEx). | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ |General Information or Other |Event Number: 37543 | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ | REP ORG: COLORADO DEPT OF HEALTH |NOTIFICATION DATE: 11/21/2000| |LICENSEE: PHOENIX SURVEYS, INC. |NOTIFICATION TIME: 15:36[EST]| | CITY: BRIGHTON REGION: 4 |EVENT DATE: 12/23/1999| | COUNTY: STATE: CO |EVENT TIME: [MST]| |LICENSE#: 838-01 AGREEMENT: Y |LAST UPDATE DATE: 11/21/2000| | DOCKET: |+----------------------------+ | |PERSON ORGANIZATION | | |GAIL GOOD R4 | | | | +------------------------------------------------+ | | NRC NOTIFIED BY: TIM BONZER (fax) | | | HQ OPS OFFICER: BOB STRANSKY | | +------------------------------------------------+ | |EMERGENCY CLASS: N/A | | |10 CFR SECTION: | | |NAGR AGREEMENT STATE | | | | | | | | | | | | | | +------------------------------------------------------------------------------+ EVENT TEXT +------------------------------------------------------------------------------+ | AGREEMENT STATE REPORT - ABANDONED WELL LOGGING SOURCE | | | | "Date of Occurrence: 12-23-99. | | | | "Description of Source: Am241Be sealed source Gulf Nuclear model: 712A, | | serial number: | | 635B, physical form: Solid, quantity: 20Ci. | | | | "Well Operator: Colorado Energy Minerals, Inc. | | | | "Well Name: UPRC Baur 17-1 | | | | "Surface Location: NW NE 600' FNL 2000' EEL Sec-17, Twp-9N, Rge-64W. | | | | "Results of efforts to seal and immobilize the source: The source is at the | | bottom of the hole with 100' of red cement above. A used drill bit has been | | cemented in as a deflector in one of the uphole plugs. | | | | "Description of attempted recovery: It was discovered the source was in the | | hole without the protection of the pad carrier. It was verified with a gamma | | ray to be on the bottom of the hole. Fishing was attempted via the wireline | | with a magnet since the holder was magnetic. These attempts were hampered by | | steadily deteriorating hole conditions and fill on top of the source. | | Fishing attempts involving use of the drilling rig and pipe were ruled out | | due to the possibility of source rupture from the extreme weight of the | | drill string. When the fishing attempts proved unsuccessful it was | | determined to cement the source in the hole. A final gamma ray was ran to | | assure the source was at the bottom of the hole and the well was plugged as | | outlined above. Note: The well was a dry hole and the well was plugged with | | cement plugs at various depths and the deflector cemented in one of these | | plugs. | | | | "Depth of the source: 4420'" | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ |Power Reactor |Event Number: 37544 | +------------------------------------------------------------------------------+ +------------------------------------------------------------------------------+ | FACILITY: HOPE CREEK REGION: 1 |NOTIFICATION DATE: 11/21/2000| | UNIT: [1] [] [] STATE: NJ |NOTIFICATION TIME: 16:12[EST]| | RXTYPE: [1] GE-4 |EVENT DATE: 11/21/2000| +------------------------------------------------+EVENT TIME: 13:08[EST]| | NRC NOTIFIED BY: ART BREADY |LAST UPDATE DATE: 11/21/2000| | HQ OPS OFFICER: BOB STRANSKY +-----------------------------+ +------------------------------------------------+PERSON ORGANIZATION | |EMERGENCY CLASS: N/A |CURTIS COWGILL R1 | |10 CFR SECTION: | | |AIND 50.72(b)(2)(iii)(D) ACCIDENT MITIGATION | | |NLCO TECH SPEC LCO A/S | | | | | | | | +-----+----------+-------+--------+-----------------+--------+-----------------+ |UNIT |SCRAM CODE|RX CRIT|INIT PWR| INIT RX MODE |CURR PWR| CURR RX MODE | +-----+----------+-------+--------+-----------------+--------+-----------------+ |1 N Y 100 Power Operation |100 Power Operation | | | | | | | +------------------------------------------------------------------------------+ EVENT TEXT +------------------------------------------------------------------------------+ | BOTH TRAINS OF CONTROL ROOM EMERGENCY FILTRATION INOPERABLE SIMULTANEOUSLY | | | | "At 1308 hours, the 'B' Control Room Chiller tripped on an apparent high | | bearing oil temperature condition, rendering the 'B' Control Room Emergency | | Filtration (CREF) train inoperable. At the time that the 'B' CREF train | | tripped, the 'A' CREF train was out of service for scheduled maintenance. | | With both trains of CREF inoperable, Technical Specification 3.0.3 was | | entered. Preparations were made to commence plant shutdown in parallel with | | restoration of the 'A' train from maintenance. The 'A' CREF train was | | returned to operable status at 1402 hours and Technical Specification 3.0.3 | | was exited. A seven-day action statement remains in effect for the | | inoperability of the 'B' CREF train. | | | | "The Control Room Ventilation System provides heating, cooling, ventilation, | | and environmental control for the control room and adjacent areas. Under | | accident conditions, the Control Room Emergency Filtration Unit ensures that | | the control room will remain habitable during and following all design basis | | accidents. Because the CREF system is required to automatically respond in | | the event of a design basis accident, having both trains of CREF inoperable | | at the same time impacted the ability to mitigate the consequences of an | | accident. Therefore, this event is being reported in accordance with | | 10CFR50.72(b)(2)(iii)(D). | | | | "All other safety related equipment is operable with the exception of the | | 'C' Main Steam Line Radiation Monitor, which is in the tripped condition due | | to a surveillance test failure. A root cause investigation team has been | | assembled to determine required corrective actions." | | | | The NRC resident inspector has been informed of this notification by the | | licensee. | +------------------------------------------------------------------------------+
Page Last Reviewed/Updated Thursday, March 25, 2021
Page Last Reviewed/Updated Thursday, March 25, 2021