Skip to main content

Alert

The NRC is shutdown due to the lapse in appropriations. Exempted activities to maintain critical health and safety activities and progress on critical activities, including activities outlined in Executive Order 14300, as described in the OMB Approved NRC Lapse Plan will continue.

Event Notification Report for March 30, 1999

                    U.S. Nuclear Regulatory Commission
                              Operations Center

                              Event Reports For
                           03/29/1999 - 03/30/1999

                              ** EVENT NUMBERS **

35400  35513  35517  35521  35522  35523  35524  35525  

!!!!!!!!! THIS EVENT HAS BEEN RETRACTED. THIS EVENT HAS BEEN RETRACTED  !!!!!!!
+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   35400       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: VERMONT YANKEE           REGION:  1  |NOTIFICATION DATE: 02/24/1999|
|    UNIT:  [1] [] []                 STATE:  VT |NOTIFICATION TIME: 19:19[EST]|
|   RXTYPE: [1] GE-4                             |EVENT DATE:        02/24/1999|
+------------------------------------------------+EVENT TIME:        19:07[EST]|
| NRC NOTIFIED BY:  JIM BROOKS                   |LAST UPDATE DATE:  03/29/1999|
|  HQ OPS OFFICER:  FANGIE JONES                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |RICHARD BARKLEY      R1      |
|10 CFR SECTION:                                 |                             |
|AOUT 50.72(b)(1)(ii)(B)  OUTSIDE DESIGN BASIS   |                             |
|NLCO                     TECH SPEC LCO A/S      |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          Y       100      Power Operation  |100      Power Operation  |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| TORUS WATER LEVEL DETERMINED TO BE OUTSIDE DESIGN BASIS DUE TO INSTRUMENT    |
| ERROR                                                                        |
|                                                                              |
| The following text is a portion of a facsimile received from the licensee:   |
|                                                                              |
| "During the design installation of a more accurate narrow range torus level  |
| instrument, as part of our [basis for maintaining operations] process, it    |
| was identified that the current level indication was 1.5 inches lower than   |
| actual level.  Under these conditions we had the potential to be slightly    |
| outside the acceptable torus operating level band high.  At this time, we    |
| are within the Tech Spec limit but outside our administrative limit.  With   |
| the 1.5-inch discrepancy, it is likely that in the past we have unknowingly  |
| operated outside the Tech Spec limit for more than 24 hours.                 |
|                                                                              |
| "We don't feel that this is of a significant safety concern since even with  |
| the 1.5-inch error, the torus level would only have been approximately 1/2   |
| inch outside the Tech Spec limit.  This would still be greater than three    |
| feet below a level where emergency depressurization would be required by the |
| emergency operating procedures.                                              |
|                                                                              |
| "The new indication installed by the design process has been declared        |
| operable, and the instrument in error                                        |
| has been declared inoperable.  The plant has entered a 24-hour shutdown      |
| [limiting condition for operation (LCO)] for being outside our               |
| administrative limit as required by plant procedures.  Plans are in place to |
| lower torus water level to within administrative limits and exit the 24-hour |
| LCO."                                                                        |
|                                                                              |
| The licensee notified the NRC Resident Inspector.                            |
|                                                                              |
| * * * RETRACTION 1011 3/29/1999 FROM SALTWELL TAKEN BY STRANSKY * * *        |
|                                                                              |
| "VY has been operating since its 05/98 outage with an administrative limit   |
| that credited in-place torus narrow-range level instrument uncertainties as  |
| <= 1.0 inches.  On 02/24/99, VY installed a new torus water level indication |
| system.  Upon energizing the new level indication system, it was noted that  |
| there existed a disparity between the in-place/operable level indication     |
| instrumentation and the new instrument.  The difference between the original |
| and operable level indication, and the newly installed instrument was        |
| approximately 1.5 inches.  It was believed at that time that the new         |
| instrument indication was very close to actual torus level.                  |
|                                                                              |
| "Upon observing the variance between the new and old indications, VY made    |
| the conservative determination that the new instrument was indicating actual |
| torus level, completed the necessary testing, declared the new system        |
| operable, and began controlling level based upon that indication.            |
|                                                                              |
| "It was concluded that the instrument uncertainty must have been             |
| significantly higher than the 1 inch credited for operation following the    |
| 05/98 outage, indicating up to 1.5 inches below actual level.  Were this     |
| true VY would have been operating with a torus water volume greater than     |
| allowed by its Technical Specifications for periods greater than those       |
| Technical Specifications allow.  It was further concluded that such          |
| operation may have invalidated the conclusions of several VY calculations    |
| and analyses which demonstrate the adequacy of the VY Primary Containment    |
| System.  VY therefore made an ENS notification for operation outside of the  |
| design basis of the plant.                                                   |
|                                                                              |
| "On 02/25/99, VY installed, and placed in service, a second high accuracy    |
| torus level indication instrument.  The two new instruments unexpectedly     |
| showed a 0.5 inch difference between one another.  The 1 inch administrative |
| margin to TS maximum and minimum levels were still in place; therefore,      |
| there was no immediate operability concern.                                  |
|                                                                              |
| "An evaluation was performed on 03/11/99 using temporary stand-pipes to      |
| determine the actual torus water level and thereby determine the accuracy of |
| the newly installed instrumentation.  That evaluation concluded that the     |
| first new instrument (activated on 02/24/99) had been consistently           |
| indicating approximately 0.5 inches higher than actual level.                |
|                                                                              |
| "This evaluation revealed that the report made on 02/24/99 was not required. |
| The actual instrument inaccuracy identified on 03/11/99 indicated that the   |
| administrative limits in place since the 05/98 outage accounted for all but  |
| 0.08 inches of the maximum error observed in the instrumentation used to     |
| control torus water volume.                                                  |
|                                                                              |
| "Plant operating logs taken since the 05/98 plant start up were reviewed.    |
| The logs show that VY operated consistent with its Technical                 |
| Specifications.                                                              |
|                                                                              |
| "The maximum error observed (0.08 inches) was evaluated in light of the      |
| analyses and calculations used to verify the adequacy of the Vermont Yankee  |
| Primary Containment.  In no case did this minor variance challenge the       |
| conclusions of any of the analyses/calculations.                             |
|                                                                              |
| "Therefore, it was concluded that the conditions were not inconsistent with  |
| the design bases of the VY plant, and the report made on 02/24/99 is being   |
| retracted."                                                                  |
|                                                                              |
| The licensee will inform the NRC resident inspector of this retraction.      |
| Notified R1DO (K. Modes).                                                    |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Fuel Cycle Facility                              |Event Number:   35513       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: PORTSMOUTH GASEOUS DIFFUSION PLANT   |NOTIFICATION DATE: 03/25/1999|
|   RXTYPE: URANIUM ENRICHMENT FACILITY          |NOTIFICATION TIME: 18:16[EST]|
| COMMENTS: 2 DEMOCRACY CENTER                   |EVENT DATE:        03/25/1999|
|           6903 ROCKLEDGE DRIVE                 |EVENT TIME:        10:03[EST]|
|           BETHESDA, MD 20817    (301)564-3200  |LAST UPDATE DATE:  03/29/1999|
|    CITY:  PIKETON                  REGION:  3  +-----------------------------+
|  COUNTY:  PIKE                      STATE:  OH |PERSON          ORGANIZATION |
|LICENSE#:  GDP-2                 AGREEMENT:  N  |MELVYN LEACH         R3      |
|  DOCKET:  0707002                              |ROBERT PIERSON       NMSS    |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  J. B. HALCOMB                |                             |
|  HQ OPS OFFICER:  FANGIE JONES                 |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          N/A                   |                             |
|10 CFR SECTION:                                 |                             |
|NCFR                     NON CFR REPORT REQMNT  |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| VALID ACTUATION OF A 'Q' SAFETY SYSTEM                                       |
|                                                                              |
| "At 1003 hours on March 25, 1999, during normal charging of cell 31-3-3      |
| prior to placing onstream, an Operations                                     |
| Front Line Manager was investigating a Cascade Automatic Data Processing     |
| smokehead alarm from this cell when a second smokehead alarmed.  He than saw |
| what appeared to be smoke above the Stage 6 area.                            |
|                                                                              |
| "All personnel in the area immediately evacuated, implemented the 'See &     |
| Flee' Procedure, activated the building recall system, and notified          |
| Emergency Response Forces.  The cell was taken offstream and cell pressure   |
| was reduced below atmosphere.                                                |
|                                                                              |
| "All airborne and surface contamination sample results were less than        |
| detectable and there was no release of                                       |
| Hazardous/Radioactive material or Radioactive/Radiological contamination     |
| exposure as a result of this event."                                         |
|                                                                              |
| The facility notified the NRC Resident Inspector and the DOE Site Manager.   |
|                                                                              |
| * * * UPDATE 1112 3/29/1999 FROM VANDERPOOL TAKEN BY STRANSKY * * *          |
|                                                                              |
| The original report was reissued with the following change to the third      |
| paragraph above:                                                             |
|                                                                              |
| "All airborne and surface contamination sample results were less than        |
| detectable, and there was no  Radioactive/Radiological contamination         |
| exposure as a result of this event."                                         |
|                                                                              |
| HOO notified R3DO (Ring).                                                    |
+------------------------------------------------------------------------------+

!!!!!!!!! THIS EVENT HAS BEEN RETRACTED. THIS EVENT HAS BEEN RETRACTED  !!!!!!!
+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   35517       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: PERRY                    REGION:  3  |NOTIFICATION DATE: 03/27/1999|
|    UNIT:  [1] [] []                 STATE:  OH |NOTIFICATION TIME: 07:04[EST]|
|   RXTYPE: [1] GE-6                             |EVENT DATE:        03/27/1999|
+------------------------------------------------+EVENT TIME:        06:05[EST]|
| NRC NOTIFIED BY:  ALAN RABENOLD                |LAST UPDATE DATE:  03/29/1999|
|  HQ OPS OFFICER:  BOB STRANSKY                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |MELVYN LEACH         R3      |
|10 CFR SECTION:                                 |                             |
|ASHU 50.72(b)(1)(i)(A)   PLANT S/D REQD BY TS   |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|1     N          N       0        Hot Shutdown     |0        Hot Shutdown     |
|                                                   |                          |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| RHR PUMP FAILS TO START                                                      |
|                                                                              |
| While attempting to place the unit onto RHR shutdown cooling, the 'A' RHR    |
| pump failed to start. The unit is currently in Condition 3 at 227�F, and the |
| main condenser is being used to remove decay heat. The licensee suspects     |
| that the failure of the pump to start may be due to a problem with a pump    |
| interlock. The licensee is currently troubleshooting the pump.               |
|                                                                              |
| The licensee entered Technical Specification Action Statement 3.0.3 due to   |
| the unavailability of shutdown cooling loop 'A'. The unit was shut down      |
| overnight in order to commence a refueling outage. The licensee will inform  |
| the NRC resident inspector of this report.                                   |
|                                                                              |
| ***RETRACTION ON 03/29/99 AT 1603 ET BY S. SANFORD TAKEN BY MACKINNON***     |
|                                                                              |
| At 0704, an entry was made into Technical Specification 3.0.3 due to the 1   |
| hour action of not verifying that a second alternate decay heat removal      |
| system was available within the 1 hour.  A 1 hour non-emergency report was   |
| made to the NRC under 50.72 (b)(1)(I)(A), Tech Spec shutdown. The reactor    |
| was already shutdown, and this event is not reportable under this criterion. |
| This is in accordance with the guidance in NUREG 1022, Event Reporting       |
| Guidelines 10 CFR 50.72 and 50.73.                                           |
|                                                                              |
| The Technical Specification bases states that "it is also required to reduce |
| reactor temperature to the point where mode 4 is entered." This statement    |
| was incorrectly determined to apply to the requirements of a Decay Heat      |
| Removal  system.  The "it" in this case refers to the requirement of the     |
| required action A.3 to be in mode 4 within 24 hours.                         |
|                                                                              |
| Therefore, the action requirement to have TWO Alternate Decay Heat Removal   |
| methods to maintain or reduce temperature was met within the required time   |
| limit of 1 hour.  The entry into Technical Specification 3.0.3 was not       |
| required.                                                                    |
|                                                                              |
| The failure of RHR "A" to start was determined to be a faulty optical        |
| isolator in the suction path logic, which was replaced. The RHR "A"          |
| subsystem was restarted in the Shutdown Cooling mode, and Mode 4 was reached |
| at 1148 hours.  R3DO (Mark Ring) notified.                                   |
|                                                                              |
| The NRC Resident Inspector was notified of this retraction by the licensee.  |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|General Information or Other                     |Event Number:   35521       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG:  ILLINOIS DEPT OF NUCLEAR SAFETY      |NOTIFICATION DATE: 03/29/1999|
|LICENSEE:  PROVENA- ST JOSEPH MED CTR           |NOTIFICATION TIME: 08:57[EST]|
|    CITY:  JOLIET                   REGION:  3  |EVENT DATE:        03/25/1999|
|  COUNTY:                            STATE:  IL |EVENT TIME:             [CST]|
|LICENSE#:  IL-01326-01           AGREEMENT:  Y  |LAST UPDATE DATE:  03/29/1999|
|  DOCKET:                                       |+----------------------------+
|                                                |PERSON          ORGANIZATION |
|                                                |PATRICK HILAND       R3      |
|                                                |LARRY CAMPER         NMSS    |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  PATRICIA LARKINS (OSP)       |                             |
|  HQ OPS OFFICER:  BOB STRANSKY                 |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          N/A                   |                             |
|10 CFR SECTION:                                 |                             |
|NAGR                     AGREEMENT STATE        |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| AGREEMENT STATE REPORT                                                       |
|                                                                              |
| The following is a compilation of information sent to the Operations Center  |
| by the Office of State Programs:                                             |
|                                                                              |
| The RSO from the Provena-St. Joseph Medical Center reported that a decay     |
| error involving an HDR source resulted in a 31% underdose to three patients  |
| (53 year old female, 43 year old female, and 60 year old male). The apparent |
| cause was the use of the certificate activity instead of the current         |
| activity for the dose planning.  The device was a Nucletron Microselectron   |
| HDR with an Ir-192 source.  The source had recently been replaced by         |
| Nucletron.                                                                   |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   35522       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: BRUNSWICK                REGION:  2  |NOTIFICATION DATE: 03/29/1999|
|    UNIT:  [] [2] []                 STATE:  NC |NOTIFICATION TIME: 11:35[EST]|
|   RXTYPE: [1] GE-4,[2] GE-4                    |EVENT DATE:        03/29/1999|
+------------------------------------------------+EVENT TIME:        08:37[EST]|
| NRC NOTIFIED BY:  MARK SCHALL                  |LAST UPDATE DATE:  03/29/1999|
|  HQ OPS OFFICER:  BOB STRANSKY                 +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |MARK LESSER          R2      |
|10 CFR SECTION:                                 |                             |
|ARPS 50.72(b)(2)(ii)     RPS ACTUATION          |                             |
|AESF 50.72(b)(2)(ii)     ESF ACTUATION          |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|                                                   |                          |
|2     A/R        Y       97       Power Operation  |0        Hot Shutdown     |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| AUTOMATIC TURBINE TRIP/REACTOR SCRAM DUE TO SPURIOUS HIGH VIBRATION SIGNAL   |
|                                                                              |
| The unit received an automatic turbine trip/reactor scram due to a suspected |
| spurious turbine high vibration signal. Following the scram, all control     |
| rods inserted, and all systems functioned as expected. Two safety/relief     |
| valves lifted but immediately reseated. Primary Containment Isolation System |
| (PCIS) Group 2 (drywell equipment and floor drains, TIP, radwaste, and       |
| process sampling), 6 (containment atmosphere and post-accident sampling),    |
| and 8 (RHR shutdown cooling) isolations occurred due to reactor vessel water |
| level shrinkage following the scram.  Reactor vessel water level recovered   |
| shortly after the scram.                                                     |
|                                                                              |
| The licensee is currently investigating the cause of the turbine vibration   |
| signal. The NRC resident inspector has been informed of this event by the    |
| licensee.                                                                    |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Other Nuclear Material                           |Event Number:   35523       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG:  FLORIDA BUREAU OF RADIATION CONTROL  |NOTIFICATION DATE: 03/29/1999|
|LICENSEE:  H.W. LOCHNER                         |NOTIFICATION TIME: 12:45[EST]|
|    CITY:  CLEARWATER               REGION:  2  |EVENT DATE:        03/29/1999|
|  COUNTY:                            STATE:  FL |EVENT TIME:             [EST]|
|LICENSE#:  2333-1                AGREEMENT:  Y  |LAST UPDATE DATE:  03/29/1999|
|  DOCKET:                                       |+----------------------------+
|                                                |PERSON          ORGANIZATION |
|                                                |MARK LESSER          R2      |
|                                                |FRED COMBS           NMSS    |
+------------------------------------------------+                             |
| NRC NOTIFIED BY:  CHARLES ADAMS                |                             |
|  HQ OPS OFFICER:  JOHN MacKINNON               |                             |
+------------------------------------------------+                             |
|EMERGENCY CLASS:          N/A                   |                             |
|10 CFR SECTION:                                 |                             |
|NAGR                     AGREEMENT STATE        |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| - AGREEMENT STATE REPORT - TROXLER MOISTURE DENSITY GAUGE RUN OVER -         |
|                                                                              |
| While taking a measurement, a Troxler #3440 gauge (serial number 029358) was |
| run over by a dump truck.  The handle was broken off, and the source could   |
| not be retracted into the case.  The source was extended approximately 12    |
| inches.  Investigators responded and put a pig over the source and           |
| transported the gauge to the state environmental lab.  The gauge was placed  |
| in the Radioactive Activity Material storage facility until the owner can    |
| get a special shipping case from Troxler:  to return the gauge for repair.   |
| Any further actions are referred to Materials Licensing.  The licensee is    |
| the H. W. Lochner facility is located in Clearwater, Florida.                |
|                                                                              |
| Troxler Model #3440 contains 8 mCi of Cesium-137 and 40 mCi of               |
| Americium-241/Beryllium.                                                     |
|                                                                              |
| Call the NRC Operations Officer for contact numbers.                         |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|General Information or Other                     |Event Number:   35524       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| REP ORG:  COGEMA MINING, INC.                  |NOTIFICATION DATE: 03/29/1999|
|LICENSEE:  COGEMA MINING, INC.                  |NOTIFICATION TIME: 16:15[EST]|
|    CITY:  Linch                    REGION:  4  |EVENT DATE:        03/26/1999|
|  COUNTY:  Campbell                  STATE:  WY |EVENT TIME:        12:00[MST]|
|LICENSE#:                        AGREEMENT:  N  |LAST UPDATE DATE:  03/29/1999|
|  DOCKET:                                       |+----------------------------+
|                                                |PERSON          ORGANIZATION |
|                                                |LINDA HOWELL         R4      |
|                                                |SCOTT MOORE          NMSS    |
+------------------------------------------------+JOE HOLONICH         NMSS    |
| NRC NOTIFIED BY:  JOHN VASELIN                 |JOHN MORRIS          DOE     |
|  HQ OPS OFFICER:  JOHN MacKINNON               |M. ROBERTSON, NRC    EPA     |
+------------------------------------------------+G. BICKERTON         USDA    |
|EMERGENCY CLASS:          N/A                   |                             |
|10 CFR SECTION:                                 |                             |
|NONR                     OTHER UNSPEC REQMNT    |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+------------------------------------------------------------------------------+

                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| SPILLED 60,918 GALLONS OF WATER CONTAINING 1.0 mg/l OF URANIUM ON 03/26/99   |
| AND SPILLED 23,520 GALLONS OF WATER CONTAINING LESS THAN 0.4 mg/l OF URANIUM |
| ON 03/29/99                                                                  |
|                                                                              |
| This event was called in under as a 48 hour report per Cogema Mining, Inc.,  |
| license.                                                                     |
|                                                                              |
| Two spills of injection mining solution recently occurred at the Christensen |
| Mine in Campbell County Wyoming. Both spills were located in Mine Unit 3     |
| which is currently in restoration and resulted from plumbing failures.  The  |
| following data summarizes the spills:                                        |
|                                                                              |
| Date                                  Location                               |
| Estimated                        Uranium                                     |
| Gallons                                mg/l                                  |
|                                                                              |
| 03/26/99                           Well H17-1                         60,918 |
| 1.0                                                                          |
|                                                                              |
| 03/29/99                             Module bldg 3-1              23,520     |
| <0.4                                                                         |
|                                                                              |
| For purposes of reporting spills, the NRC license considers any spill of     |
| 10,000 gallons of more to be significant from an operations standpoint,      |
| regardless of the chemical and radioactive characteristics of the spill.     |
| Therefore, both spills are reported.                                         |
|                                                                              |
| Health and Environmental Hazards:   None expected.  The solution does not    |
| pose a health or environmental hazard and did not leave the NRC permitted    |
| area.  Note that the nearest community is Linch, Wyoming, approximately 15   |
| miles to the southwest.                                                      |
|                                                                              |
| Corrective Actions:    Well H17-1:  Well was shut down until the plumbing    |
| failure can be repaired.                                                     |
| Available spill solution is being recovered.                                 |
|                                                                              |
| Module building 3-1:  The plumbing failure was repaired and flow is back on  |
| line.                                                                        |
|                                                                              |
| Soil samples have been collected at both spill locations and will be         |
| analyzed for Ra-226 to determine if soil clean-up is needed.                 |
|                                                                              |
| Written Notification:  A written notification giving further details will be |
| submitted to the NRC Uranium Recovery  Branch Chief within 7 days.           |
+------------------------------------------------------------------------------+

+------------------------------------------------------------------------------+
|Power Reactor                                    |Event Number:   35525       |
+------------------------------------------------------------------------------+
+------------------------------------------------------------------------------+
| FACILITY: BEAVER VALLEY            REGION:  1  |NOTIFICATION DATE: 03/29/1999|
|    UNIT:  [] [2] []                 STATE:  PA |NOTIFICATION TIME: 20:22[EST]|
|   RXTYPE: [1] W-3-LP,[2] W-3-LP                |EVENT DATE:        03/29/1999|
+------------------------------------------------+EVENT TIME:        18:01[EST]|
| NRC NOTIFIED BY:  TOM COTTER                   |LAST UPDATE DATE:  03/29/1999|
|  HQ OPS OFFICER:  JOHN MacKINNON               +-----------------------------+
+------------------------------------------------+PERSON          ORGANIZATION |
|EMERGENCY CLASS:          N/A                   |KATHLEEN MODES       R1      |
|10 CFR SECTION:                                 |STUART RICHARDS      NRR     |
|AESF 50.72(b)(2)(ii)     ESF ACTUATION          |FRANK CONGEL         IRO     |
|                                                |                             |
|                                                |                             |
|                                                |                             |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|UNIT |SCRAM CODE|RX CRIT|INIT PWR|   INIT RX MODE  |CURR PWR|  CURR RX MODE   |
+-----+----------+-------+--------+-----------------+--------+-----------------+
|                                                   |                          |
|2     N          N       0        Cold Shutdown    |0        Cold Shutdown    |
|                                                   |                          |
+------------------------------------------------------------------------------+
                                   EVENT TEXT                                   
+------------------------------------------------------------------------------+
| PARTIAL LOSS OF POWER DUE TO 4.10KV BUS UNIT STATION SERVICE TRANSFORMER     |
| SUPPLY OVERCURRENT TRIP. EMERGENCY DIESEL GENERATOR 2-1 SUPPLYING POWER TO   |
| VITAL BUS "AE".                                                              |
|                                                                              |
| At 1801 hours, "4160V Bus Unit Station Service Transformer Supply            |
| Overcurrent Trip" alarm was received. This alarm indicates that the supply   |
| breaker, 42C, to the normal 4kV bus "2A" opened and deenergized the bus. The |
| "2A" bus supplies train "A" emergency 4kV bus "AE" so it also deenergized.   |
| The emergency diesel generator 2-1 started and reenergized the "AE"          |
| emergency bus.  The "B" train of electrical power and safeguards equipment   |
| remained fully operable, the emergency diesel generator is fully operable if |
| needed.  Prior to the overcurrent trip, the plant was in mode 5 (cold        |
| shutdown) with Reactor Coolant System temperature at 97�F and 280 psig.      |
| Their was no interruption to core cooling during the event.  Core cooling    |
| was being provided by the "B" train of the residual heat removal system and  |
| was unaffected.  Both trains of residual heat removal remain operable.  The  |
| site maintenance department is evaluating the cause for the relay protection |
| actuation.  The 2-1 emergency diesel generator will continue to supply the   |
| emergency bus until this investigation is completed and normal power is      |
| restored.  The vital buses cannot be cross connected and emergency diesel    |
| generator 2-1 has plenty of fuel to keep it operating.   Spent fuel pool     |
| cooling was not lost.                                                        |
|                                                                              |
| Offsite power is stable, and the other emergency bus "2DF" can supply enough |
| electrical power to safe plant operation while shutdown if electrical power  |
| is lost from emergency bus "2AE".                                            |
|                                                                              |
| The NRC Resident Inspector was notified of this event by the licensee.       |
+------------------------------------------------------------------------------+


Page Last Reviewed/Updated Thursday, March 25, 2021

Page Last Reviewed/Updated Thursday, March 25, 2021