Skip to main content

Alert

The NRC is shutdown due to the lapse in appropriations. Exempted activities to maintain critical health and safety activities and progress on critical activities, including activities outlined in Executive Order 14300, as described in the OMB Approved NRC Lapse Plan will continue.

EA-96-532 - Dresden 2 & 3 (Commonwealth Edison Company

May 21, 1997

EA 96-532

Mr. J. S. Perry
Site Vice President
Dresden Station
Commonwealth Edison Company
6500 North Dresden Road
Morris, IL 60450

SUBJECT: NOTICE OF VIOLATION (NRC RESIDENT INSPECTION REPORT 50-010/237/249/96014(DRP))

Dear Mr. Perry:

This refers to the inspection conducted from October 21 through December 6, 1996, at the Dresden Station Unit 2 and 3 facilities. The inspection included a review of the failure to adequately test the control room emergency ventilation system to ensure it conformed to its design basis. The written results of this inspection were provided to you on February 4, 1997. A predecisional enforcement conference was conducted on February 28, 1997.

Based on the information developed during the inspection and the information that you and your staff provided during the conference, the NRC has determined that a violation of NRC requirements occurred. The violation is cited in the enclosed Notice of Violation (Notice) and the circumstances surrounding it are described in detail in the subject inspection report. The control room ventilation system had not been maintained or properly tested to ensure that the system operated within its design basis, and was declared inoperable on October 8, 1996. Several control room modifications, which had not been completed, contributed to the inability to pressurize the control room as stated in the Updated Final Safety Analysis Report (UFSAR). The modifications resulted in the inability to maintain the control room at a positive pressure during normal operations and at a positive pressure of 1/8-inch water-gauge (iwg) during emergency pressurization modes, with respect to adjacent areas.

Post modification testing was not performed for a 1989 modification of the Unit 1 to Unit 2/3 control room fire-wall. Following the completion of this modification in May 1993, inadequate surveillance tests were performed on the emergency ventilation system. Specifically, the surveillance procedure only required 1/8 iwg positive pressure in the control room and did not ensure that pressure was greater than 1/8 iwg for the surrounding areas. In addition, instrumentation used to verify that the control room pressure was positive in the emergency mode had not been calibrated, and had not been installed in accordance with the piping and instrumentation diagram. The instrumentation used to verify the control room differential pressure also was not calibrated and was not verified to be appropriate for the parameters being measured. Control room instrumentation was mislabeled with respect to the areas being sensed and, according to the drawings, other sensing lines were not properly routed or were broken.

The safety significance of this issue was related to the potentially increased radiological consequences to control room operators during a postulated design basis accident. Since the ventilation system was unable to maintain the required positive pressure during the emergency modes, an increased inleakage was likely to occur during the design basis accident. Using this increased inleakage in conjunction with the dose calculation performed in the UFSAR, the dose limits established by 10 CFR 50, Appendix A, General Design Criterion 19 for control room operators potentially would have been exceeded. The barriers in place to ensure these limits would not be exceeded failed. Specifically, post-modification testing was not performed, and surveillance testing was inadequate. While this condition was identified on September 26, 1996, it is possible that the control room emergency ventilation system had not met its design basis since the 1989 modification was completed. In addition, from January 16 to May 28, 1995, leakage from the Unit 3 main steam line drain primary containment isolation valves would have exceeded accident analysis assumptions during a postulated design basis accident. During this period, it is quite likely that the accident dose to control room operators would have exceeded regulatory requirements.

The failure to perform post-modification testing of the control room emergency ventilation system to ensure design requirements were maintained is of concern because design modification testing controls were inadequate to ensure that system operability was maintained. In addition, engineering backlog reviews conducted by your staff in the spring of 1996 failed to identify the potential for significant system degradation due to the open control room modification packages. As a result, the control room was found not capable of maintaining the required positive pressure or in-leakage limitations. The as-found degradation was significant in that the potential may have existed for control room radiological doses to be in excess of regulatory limits following a design basis accident. Therefore, this violation has been categorized in accordance with the "General Statement of Policy and Procedure for NRC Enforcement Actions" (Enforcement Policy), NUREG-1600 at Severity Level III.

In accordance with the Enforcement Policy, a base civil penalty in the amount of $50,000 is considered for a Severity Level III violation. Because Dresden Station has been the subject of escalated enforcement actions within the last 2 years, the NRC considered whether credit was warranted for Identification and Corrective Action in accordance with the civil penalty assessment process in Section VI.B.2 of the Enforcement Policy. The NRC determined that credit for Identification was warranted because on September 26, 1996, while closing out the open 1989 modification, the cognizant system engineer noted that there was no differential pressure between the control room and the outside hallway. This observation prompted the performance of a test to determine the actual control room to outside air differential pressure. On October 7, 1996, when the testing was performed, it was determined that the system was unable to maintain the required positive 1/8 iwg pressure in the control room with respect to all adjacent areas. The system was declared inoperable on October 8, 1997. The NRC determined that credit for Corrective Action was warranted based on your staff's prompt and thorough corrective actions. Immediate corrective actions included sealing system duct work and control room emergency zone penetrations, removing wallboard and cabinets to allow access to walls for leak identification and sealing, and properly identifying installed instrumentation. Dresden personnel also notified Quad Cities of potential problems with adequacy of control room emergency ventilation system testing. The control room ventilation system was restored to full operability on January 21, 1997, after the repairs were completed, the pressurization requirements were verified, the control room differential pressure instruments were repaired, the original test engineer qualifications were revoked, management oversight was improved, and the post modification testing program was improved.

Therefore, to encourage prompt identification and comprehensive correction of violations, I have been authorized, after consultation with the Director, Office of Enforcement, not to propose a civil penalty in this case. However, significant violations in the future could result in a civil penalty.

The NRC has concluded that information regarding the reason for the violation, the corrective actions taken and planned to correct the violation and prevent recurrence and the date when full compliance was achieved is already adequately addressed on the docket in LER 96-017, as supplemented, and the information you provided at the predecisional enforcement conference which is attached to our letter to you dated March 26, 1997. Therefore, you are not required to respond to this letter unless the description therein does not accurately reflect your corrective actions or your position. In that case, or if you choose to provide additional information, you should follow the instructions specified in the enclosed notice.

Sincerely, /s/ James L. Caldwell (for) A. Bill Beach Regional Administrator

Docket Nos. 50-237; 50-249
License Nos. DPR-19; DPR-25

Enclosure: Notice of Violation

cc w/encl:
T. J. Maiman, Senior Vice President
Nuclear Operations Division
D. A. Sager, Vice President,
Generation Support
H. W. Keiser, Chief Nuclear
Operating Officer
T. Nauman, Station Manager Unit 1
M. Heffley, Station Manager Units 2 and 3
F. Spangenberg, Regulatory Assurance
Manager
I. Johnson, Acting Nuclear
Regulatory Services Manager
Richard Hubbard
Nathan Schloss, Economist
Office of the Attorney General
State Liaison Officer
Chairman, Illinois Commerce Commission
Document Control Desk-Licensing


NOTICE OF VIOLATION

Commonwealth Edison Company Docket Nos. 50-237; 50-249 Dresden Station License Nos. DPR-19; DPR-25 EA 96-532

During an NRC inspection conducted from October 21 through December 6, 1996, a violation of NRC requirements was identified. In accordance with the "General Statement of Policy and Procedure for NRC Enforcement Actions," NUREG-1600, the violation is listed below:

10 CFR 50, Appendix B, Criterion XI, "Test Control," states that a test program shall be established to assure that all testing required to demonstrate that structures, systems, and components will perform satisfactorily in service is identified and performed in accordance with written test procedures which incorporate the requirements and acceptance limits contained in applicable design documents.

Updated Final Safety Analysis Report (UFSAR) section 6.4.2.4, "Interactions with Other Zones and Pressure Containing Equipment," states, in part, that potential adverse interactions between the control room emergency zone and adjacent zones that may allow transfer of toxic or radioactive gases into the control room are minimized by maintaining the control room at a positive pressure of 1/8-inch water-gauge during emergency pressurized modes, with respect to adjacent areas.

Contrary to the above, the licensee discovered that the original design modification test and subsequent surveillance tests of the control room Heating, Ventilation, and Air Conditioning system failed to ensure that the requirements and acceptance limits specified in the UFSAR, an applicable design document, section 6.4.2.4 were met. Specifically, the licensee discovered that on September 26, 1996, the control room ventilation system was not able to maintain the control room at 1/8-inch water-gauge positive pressure with respect to adjacent areas during emergency pressurized modes (01013).

This is a Severity Level III Violation (Supplement I).

The NRC has concluded that information regarding the reason for the violation, the corrective actions taken and planned to correct the violation and prevent recurrence and the date when full compliance was achieved is already adequately addressed on the docket in LER 96-017, as supplemented, and the information you provided at the predecisional enforcement conference which is attached to our letter to you dated March 26, 1997. However, you are required to sumbit a written statement or explanation pursuant to 10 CFR 2.201 if the description therein does not accurately reflect your corrective actions or your position. In that case, or if you choose to respond, clearly mark your response as a "Reply to a Notice of Violation," and send it to the U.S. Nuclear Regulatory Commission, ATTN: Document Control Desk, Washington, D.C. 20555 with a copy to the Regional Administrator, Region III and a copy to the NRC Resident Inspector at the facility that is the subject of the Notice, within 30 days of the date of the letter transmitting this Notice of Violation (Notice).

Dated at Lisle, Illinois
this 21st day of May 1997

To top of page

Page Last Reviewed/Updated Wednesday, March 24, 2021

Page Last Reviewed/Updated Wednesday, March 24, 2021